background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat 
Controllers Installation Instructions

12

Operation

Programming/Operating the TEC2604-4 or 
TEC2604-4+PIR Thermostat Controller

Once the thermostat controller is configured via the 
Installer Configuration Menu, its operating parameters 
can be programmed via the Main User Menu. Access 
this menu by pressing the 

MENU

 key during normal 

thermostat controller operation. The Main User Menu 
contains the basic operating features of the thermostat 
controller.

The Main User Menu also uses Auto Help, which is 
displayed automatically in the menu when there is a 
pause in programming activity. To exit Auto Help, 
continue with the programming selection. When the 
thermostat controller is in the Main User Menu and is 
left unattended for 45 seconds, the menu reverts to the 
Status Display Menu.

Enabling Override Schedule

Note:

Enabling Override Schedule only appears when 

in the Unoccupied Mode.

The override schedule prompt only appears when the 
thermostat controller is in the unoccupied state. This 
menu selection gives the user the option of overriding 
the unoccupied setpoints with the occupied setpoints 
for the amount of time specified under the 

TOccTime

 

parameter. See the 

Configuring the TEC2604-4 or 

TEC2604-4+PIR Thermostat Controller

 section.

Note:

If one of the digital inputs is configured to 

operate as a remote override contact, this menu is 
disabled.

Min pos

Sets the minimum position for the 
OA dampers on the economizer. 
These dampers are energized to 
minimum position when the fan 
(Terminal G) is energized and the 
thermostat controller is in the 
Occupied mode. When the 
schedule is in the Unoccupied 
mode, the minimum position is 0%.
Default: 

0.0%

Range: 

0.0

 to 

100.0%

 equals 0 to 10 VDC output range

% OA

Setting for 0 to 10 VDC 

Actuator

Setting for 2 to 10 VDC 

Actuator

(0.0%)

0%

0 to 20%

(5.0%)

5%

24%

(10.0%)

10%

28%

(15.0%)

15%

32%

(20.0%)

20%

36

%

(25.0%)

25%

40%

(30.0%)

30%

44%

C mech

Determines whether to allow 
mechanical cooling (compressor 
operation) if free cooling 
(economizer operation) cannot 
maintain the cooling setpoint.
Default: 

off

(on):

 Typically applies when the MS is installed before the 

mechanical cooling refrigeration coils in the mixing plenum. In this 
scenario, mechanical cooling is allowed when free cooling cannot 
maintain the cooling setpoint.

(off):

 Typically applies when the remote Mixed air Sensor (MS) is 

installed after the mechanical cooling refrigeration coils. In this 
scenario, mechanical cooling will never operate at the same time as 
free cooling.

Mix stpt

2

Establishes the mixed air 
temperature when operating in the 
economizer mode.
Default: 

55.0°F/13.0°C

Range: 

50.0°F/10.0°C

 to 

90.0°/32.0°C

MS temp

Displays the mixed air temperature. 
Requires that an MS be installed 
and connected.
Default: 

N/A

The mixed air temperature can be used to help service and 
troubleshoot the equipment and the economizer operation. The 
mixed air temperature is only accessible via the Installer 
Configuration Menu.

1.

When adjusting the numeric value, press the 

UP

 or 

DOWN

 arrow key to change the value by single increments; press and 

hold the 

UP

 or 

DOWN

 arrow key to change the numeric value in increments of ten.

2.

When adjusting the temperature, press the 

UP

 or 

DOWN

 arrow key to change the value in 0.5F°/0.5C° increments; press 

and hold the 

UP

 or 

DOWN

 arrow key to change the value in 5.0F°/5.0C° increments.

Table 1:  Installer Configuration Menu  (Part 5 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC2604-4

Page 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Page 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Page 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Page 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Page 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Page 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Page 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Page 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Page 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Page 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Page 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Page 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Page 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Page 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Page 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Page 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Page 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Reviews: