TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat

Controllers Installation Instructions

11

H stage

Reverts the operation of a two-stage 
thermostat controller to a single-
stage thermostat controller when 
the second heating stage is not 
needed.
Default: 

2.0

(1.0):

 One Stage

(2.0):

 Two Stages

C stage

Reverts the operation of a two-stage 
thermostat controller to a 
single-stage thermostat controller 
when the second cooling stage is 
not needed.
Default: 

2.0

(1.0):

 One Stage

(2.0):

 Two Stages

H lock

Discontinues heating operation in 
response to the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
Default: 

120°F/49°C

Range: 

-15°F/-26°C

 to 

120°F/49°C

 adjustable in 5F°/5C° 

increments

C lock

Discontinues cooling operation in 
response to the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
Default: 

-40°F/-40°C

Range: 

-40°F/-40°C

 to 

95°F/35°C

 adjustable in 5F°/5C° increments

Unocc TM

Sets the time delay between the 
moment when the thermostat 
controller toggles from the Occupied 
mode to the Unoccupied mode after 
the last motion is detected by the 
occupancy sensor.
Default: 

0.5 hours

Range: 

0.5 hours

 to 

24.0 hours

 adjustable in 0.5 hour increments

Aux cont

Energizes peripheral devices 
(lighting equipment, exhaust fans, 
and economizers).
Default: 

n.o.

(n.c.):

 Contact open = Occupied; contact closed = Unoccupied.

(n.o.):

 Contact closed = Occupied; contact open = Unoccupied.

The contact toggles with the internal Occupied/Unoccupied 
schedule (or the NSB contact on one of the digital inputs, if used).

Chngstpt

2

Sets the economizer changeover 
strategy, based on the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
When the OA temperature is below 
the changeover setpoint, free 
cooling is used (economizer 
operation). When the OA 
temperature is above the setpoint, 
mechanical cooling is used 
(compressor operation).
Default: 

55.0°F/13.0°C

Range: 

14.0°F/-10.0°C

 to 

70.0°F/21.0°C

Table 1:  Installer Configuration Menu  (Part 4 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC2604-4

Page 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Page 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Page 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Page 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Page 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Page 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Page 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Page 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Page 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Page 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Page 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Page 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Page 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Page 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Page 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Page 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Page 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Reviews: