background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat

Controllers Installation Instructions

5

The MS/TP Bus requires proper termination and 
biasing at each end of a segment (a segment is a 
physically continuous length of wire). Because the 
rooftop controller is not equipped with end-of-line 
termination, a Johnson Controls MS-BACEOL-0 End-
of-Line Terminator (see Table 3; ordered separately) or 
similar device is recommended to provide this end-of-
line termination. An end-of-line terminator is required if 
a supervisory controller is not at the end of the 
segment. If a supervisory controller is at the end of the 
segment, then the end-of-line terminator switch on the 
supervisory controller must be set in the ON position.

The thermostat controller has automatic baud rate 
detection. Do not exceed the maximum number of 
devices allowed on a field bus. Be sure that the wiring 
terminations are set correctly and that all 
communication wiring is daisy-chained with no taps.

A small green light under the thermostat controller 
cover (on the left edge when facing the thermostat 
controller) indicates the communications mode when 
the thermostat controller is operating. 

The following blink codes may be seen:

Short-Short-Long:

 Indicates that the baud rate is 

known and that communication is active.

Short-Short:

 Indicates that the thermostat 

controller is scanning for the correct baud rate and 
that there is no communication.

Off:

 Indicates that there is no power to the 

thermostat controller or that the MS/TP wiring 
polarity is reversed.

Long:

 Indicates that the MS/TP communication 

daughter board is the wrong type for the main 
board.

MS/TP Thermostat Controller Mapping

For detailed information on MS/TP Bus objects and 
thermostat controller mapping, refer to the 

TEC 

BACnet MS/TP Network Series Thermostat Controllers 
Technical Bulletin (LIT-12011592).

Setup and Adjustments

Thermostat Controller User Interface Keys

The TEC2604-4 and TEC2604-4+PIR Thermostat 
Controller user interface consists of five keys on the 
front cover (Figure 6). The function of each key is as 
follows:

Use  the 

YES

 key to:

-

confirm menu selections and to advance to the 
next menu item

-

stop the Status Display Menu from scrolling 
and to manually scroll to the next parameter on 
the menu

Note:

When the thermostat controller is left 

unattended for 45 seconds, the thermostat 
controller display resumes scrolling.

Use  the 

NO

 key to decline a parameter change and 

to advance to the next menu item.

Figure 6: Front Cover of Thermostat Controller (TEC2604-4+PIR Model Shown)

70.0ºF

Room Temp

Backlit, plain text

Liquid Crystal Display (LCD)

is easy to read in any condition.

Five keys on the thermostat controller
make operation easy and intuitive.

Light-Emitting Diodes (LEDs)
indicate system activity.

FI

G

:f

rn

t_v

w

PIR motion detector

saves energy using

standby setpoints.

Summary of Contents for TEC2604-4

Page 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Page 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Page 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Page 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Page 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Page 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Page 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Page 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Page 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Page 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Page 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Page 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Page 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Page 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Page 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Page 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Page 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Reviews: