TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions

4

Connecting the N2 Bus

To connect the N2 Bus:

1.

Set the N2 address of the TEC2101-3 Thermostat 
per the engineering drawings prior to wiring the 
thermostat. (See the 

Com addr

 parameter in 

Table 2 to set the N2 address for the thermostat.) 
Also test for N2 voltage, polarity, and isolation prior 
to wiring the thermostat.

2.

Observe the polarity when connecting the N2 Bus 
wires to the thermostat.

3.

After the N2 Bus wires are connected to the first 
thermostat, continue in a daisy-chained fashion to 
the next thermostat.

Note:

The thermostat N2 Bus is self-terminating. The 

N2 Bus wiring must be twisted-pair lines. Do not run the 
N2 Bus wiring in the same conduit as line voltage 
wiring (30 VAC or above) or other wiring that switches 
power to highly inductive loads (such as contactors, 
coils, motors, or generators).

For more N2 Bus overview information, refer to the 

N2 

Communications Bus Technical Bulletin (LIT-636018)

 

and 

ASC and N2 Bus Networking and Troubleshooting 

Technical Bulletin (LIT-6363003)

.

N2 Device Mapping

Define the TEC2101-3 Thermostat as a Vendor Device 
(VND) when adding the thermostat to the supervisory 
controller.

The Thermostat Point (Type/Address) is the fixed-point 
definition inside the thermostat. The most recent N2 
command received by any of the Object Types listed in 
Table 1 controls the thermostat.

Only one of the setpoints (either Heating SP or Cooling 
SP) can be overridden at a time. Overrides take priority 
over any local adjustment or command in the 
thermostat.

If a setpoint is overridden, the thermostat adjusts the 
other setpoint, if necessary, to maintain the minimum 
deadband between the two setpoints. The setpoints 
can be spread farther apart but can never be adjusted 
closer than 2F°/1C° apart.

If a supervisory controller commands an override of an 
analog or binary object, all local changes attempted 
through the thermostat keypad for that object are 
ignored until the override is released. For example, if 
the supervisory controller sends an override message 
to turn System Mode Off, and then the user selects 
System Mode On at the thermostat keypad, the 
thermostat keeps the System Mode Off.

When an override is released, the object may once 
again be changed through the thermostat keypad, but 
the thermostat does not retain any data entered at the 
thermostat keypad during the override.

All overrides are released automatically after 
10 minutes of no communications (for example, if the 
network cable is removed from the thermostat, causing 
a loss of network communications).

Metasys® System Person-Machine Interface (PMI)

Do not direct-map any points; instead, run control of 
these points through the Control System (CS) object. 
The supervisory controller Model Point Type is the 
definition inside the model file. Use a CS object to 
retrieve the data.

Metasys System Extended Architecture

There must not be a Relinquish Default for the 
setpoints if it is desired to change them from the 
thermostat display. If there is a Relinquish Default for 
the setpoints, the supervisory controller always has an 
Override for either an Adjusted value or the Relinquish 
Default value. Use the Operator Override and the 
Release Operator Override to command the setpoint 
and release it to local control. At that time, the user is 
able to change the setpoint from the local display.  

Table 1:  N2 Bus Objects  (Part 1 of 2)

Point Name

Thermostat Point 
(Type/Address)

N2 Bus Object 
Type

Model Point Type

Range

Room Temp

1

ADI-1

N2 AI

CSAD

32 to 122°F (0 to 50°C)

Aux Temp/Outdoor Temp

1

ADI-2

N2 AI

CSAD

-40 to 122°F 
(-40 to 50°C)

Heating SP

1,2

(Occupied Heating SP)

ADI-3

N2 AO

CSAD

40 to 90°F (4.5 to 32°C)

Cooling SP

1,2

(Occupied Cooling SP)

ADI-4

N2 AO

CSAD

54 to 100°F 
(12 to 37.5°C)

Setback Heating SP

1,2

(Unoccupied Heating SP)

ADI-5

N2 AO

CSAD

40 to 90°F (4.5 to 32°C)

Summary of Contents for TEC2101-3 N2

Page 1: ...Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Installation Location Considerations Locate the TEC2101 3 Thermostat on a partitioning wall approximately 5 ft 1 5 m above the floor in a location of average temperature ...

Page 2: ...hermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to secure the base to the surface as ill...

Page 3: ...ing all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC2101 3 Thermostat Figure 5 Wiring the TEC2101 3 Thermostat If using the same power source for the thermostat and heating loads install ...

Page 4: ...ontroller commands an override of an analog or binary object all local changes attempted through the thermostat keypad for that object are ignored until the override is released For example if the supervisory controller sends an override message to turn System Mode Off and then the user selects System Mode On at the thermostat keypad the thermostat keeps the System Mode Off When an override is rel...

Page 5: ...6 7 BI 1 N2 BI CSBI 0 Off 1 On Temp Alarm6 BI 2 N2 BI CSBI 0 Normal 1 Alarm DI26 7 BI 3 N2 BI CSBI 0 Off 1 On 1 Commandable 2 The Heating and Cooling Setpoint SP cannot be overridden simultaneously this also applies to the Setback Heating SP and Setback Cooling SP The overridden setpoint must be released prior to overriding the other setpoint Additionally if one setpoint is overridden the other se...

Page 6: ...nt is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum 2 F deadband between the setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2 F apart Failure to stay within the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2101 3 thermostat Overrides take precedence over any local adjustment or comma...

Page 7: ...cy Status Occupied Unoccupied Override Outdoor Temperature An outdoor air temperature sensor must be connected Applicable Alarms The backlight lights up as an alarm condition is displayed Note Press the YES SCROLL key to temporarily stop this menu from scrolling The Main User Menu is used to access and change the basic operating parameters of the thermostat Access this menu by pressing the MENU ke...

Page 8: ...ayed on the thermostat when the input is energized This input can be tied into the air conditioning unit control card which provides an alarm should there be a malfunction Filter A Filter alarm is displayed This alarm can be connected to a differential pressure switch that monitors a filter RemOVR Temporary occupancy request via a remote input This override function is controlled by a manual remot...

Page 9: ...3 0 or 4 0 cycles per hour Deadband Sets the minimum deadband between the heating and cooling setpoints Default 2 0F 1 0C Range 2 0F 1 0C to 4 0F 2 0C adjustable in 1 0F 0 5C increments Fan cont Determines how the fan is activated in response to a call for heating Fan cont applies to W1 and Fan Mode auto only Fan cont does not affect fan operation on a call for cooling Y1 Default on off The thermo...

Page 10: ...tdoor air temperature Requires that an outdoor air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed and connected Default 40 F 40 C Range 40 F 40 C to 95 F 35 C adjustable in 5F 5C ...

Page 11: ...nly appears when the thermostat is in the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first prompt 2 Press the YES key to resume the programmed schedule The thermostat returns to the Status Display Menu Entering Permanent Tempe...

Page 12: ... the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu Selecting the Fan Mode The thermostat has three fan mode settings On Fan Mode on Energizes the fan all the time for both occupied and unoccupied states even if the system mode is set to off Automatic Fan Mode auto Energizes the fan ...

Page 13: ...ition Possible Cause Solution Thermostat Cycles Online and Offline Two or more controllers have the same address Change each duplicate address to a unique number There are Y or T taps on the N2 Bus or the repeater has lost power or is wired incorrectly Refer to the N2 Communications Bus Technical Bulletin LIT 636018 Thermostat Does Not Come Online Two or more controllers have the same address Chan...

Page 14: ... Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Noncondensing Compliance United States UL Listed File E27734 CCN XAPX Under UL 873 Temperature Indicating and...