background image

 

Programming the Daily Schedule – Four-Event 

The schedule setting menu is used to set the occupied 
and unoccupied time periods for each day of the week. 
The schedule setting menu reflects either a two or four 
event schedule per day based on what was selected in 
the 

Selecting the Number of Events (2/4event) menu 

during the configuring process. If the schedule-setting 
menu does not reflect a four-event schedule, return to 
the 

Selecting the Number of Events (2/4event)

 menu 

in the configuration process and select four events. 

When changing the time, pressing the UP/DOWN 
arrow keys changes the time in 1-minute increments. 
Holding the keys down changes the time in 30-minute 
increments. 

Note: 

Programming one of the digital inputs to 

remote NSB disables the menu. 

Follow the steps in Table 7 to set the time schedule for 
four-event schedule. 

Table 8 shows an example of a four-event office 
schedule. 

Table 7: Programming the Daily Schedule – 
Four-Event 

 

Press MENU from the Status 
Display Menu to enter the Main User 
Menu. 

 

Answer NO to all prompts until the 
schedule set prompt appears in the 
display. Press YES to set the 
scheduling menu. 

 

Press YES to set the schedule for 
Monday or NO to advance to 
Tuesday. 

 

Press YES to set the occupied start 
time for Monday or NO to advance 
to Tuesday (selecting NO leaves the 
thermostat in the unoccupied mode 
for the entire day). 

 

Use the UP/DOWN arrow keys to 
set the first occupied start time. 
Press YES to enter the time. 

 

Use the UP/DOWN arrow keys to 
set the first unoccupied start time. 
Press YES to enter the time. 

 

Use the UP/DOWN arrow keys to 
set the second occupied start time. 
Press YES to enter the time. 

 

Use the UP/DOWN arrow keys to 
set the second unoccupied start 
time. Press YES to enter the time. 

 

Press YES to set the schedule for 
Tuesday or NO to advance to 
Wednesday. 

 

Press YES to copy the schedule 
from the previous day. Press NO to 
set a different schedule. 

 

If YES was pressed, the next prompt 
is for Wednesday. Repeat procedure 
for all days of the week. 

 

After setting the schedule for all 
days of the week, following the last 
entry for Sunday, press YES to 
return to the Status Display Menu or 
NO to start again at Monday. 

Occupied
12:00 AM 

Unoccup
12:00 AM 

Occupie2
12:00 AM

 

Unoccup2
12:00 AM

 

Tuesday
set? Y/N 

Copy Y/N
previous 

RoomTemp
75.0

°

F

 

Wednesda
set? N/A 

Schedule 
set? Y/N 

Exit?
 Y/N

 

Monday 
set? Y/N 

 

Occupied 
day? Y/N 

T600MSP-2 Programmable Thermostat Installation Instructions    

15

 

Summary of Contents for T600MSP-2

Page 1: ...t cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tab to the right Figure 2 Open the thermostat s PCB to the left 3 Pull out approximately 6 in 152 mm of wires...

Page 2: ...s and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wi...

Page 3: ...the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second s...

Page 4: ...and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Fig...

Page 5: ...ver and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Inputs DI1 and D...

Page 6: ...hen the message displays the backlight momentarily lights up TOccTime set Y N Each digital input can be programmed in one of five conditions None No function is associated with the input Service A Ser...

Page 7: ...e the Enabling Frost Protection Frost pr section for setup instructions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in...

Page 8: ...rature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to all...

Page 9: ...emporary setpoint is entered The range is adjustable from 0 to 12 hours To change the temporary occupancy time while in the Installer Configuration Menu 1 Answer NO to all prompts until the temporary...

Page 10: ...lue The display now shows the cooling lockout prompt See the Setting the Cooling Lockout C lock section for instructions Setting the Cooling Lockout C lock This feature disables cooling operation base...

Page 11: ...o the beginning of the menu digital input configuration Operation Programming Operating the T600MSP 2 Once the T600MSP 2 thermostat is configured through the Installer Configuration Menu the thermosta...

Page 12: ...does not appear Answering YES to this prompt enables the T600MSP 2 thermostat to resume the regular scheduled program and setpoints Schedule set Y N To resume the schedule while in the Main User Menu...

Page 13: ...setpoints remain in effect for the duration set in the Temporary Occupancy Time parameter TOccTime or until manually released To release the temporary setpoint sooner while in the main User Menu 1 An...

Page 14: ...ys changes the time in 1 minute increments Holding the keys down changes the time in 30 minute increments Note Programming one of the digital inputs to remote NSB disables the menu Follow the steps in...

Page 15: ...e scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermosta...

Page 16: ...press YES to store the time 4 Press YES to enter the day set menu or NO to enter the clock format menu 5 Use the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to st...

Page 17: ...al Accessories Includes Mounting Hardware 2 Use the UP DOWN arrow keys to locate the desired permanent hold type or resume schedule Press YES to enter the choice Item Product Code Number Remote Indoor...

Page 18: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protecti...

Reviews: