T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions
11
H lock
5
Disables heating stage(s) operation
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default:
120°F/49°C
Range:
-15°F/-26°C
to
120°F/49°C
adjustable in 5F°/5C° increments
C lock
5
Disables cooling stage(s) operation
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default:
-40°F/-40°C
Range:
-40°F/-40°C
to
95°F/35°C
adjustable in 5F°/5C° increments
Unocc TM
Sets the time delay between the
moment when the thermostat
controller toggles from the Occupied
mode to the Unoccupied mode after
the last motion is detected by the
occupancy sensor.
Default:
0.5 hours
Range:
0.5 hours
to
24.0 hours
adjustable in 0.5 hour increments
2/4event
2
Sets the number of events within a
24-hour period.
Default:
2.0
(4.0):
Four events (two Occupied and two Unoccupied) within a
24-hour period
(2.0):
Two events (one Occupied and one Unoccupied) within a
24-hour period
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default:
n.o.
Note:
The contact toggles with the
internal Occupied/Unoccupied
schedule (or the NSB contact on
one of the digital inputs, if used).
(n.c.):
Contact open = Occupied; contact closed = Unoccupied
(n.o.):
Contact closed = Occupied; contact open = Unoccupied
Prog rec
2
Provides the desired occupied
temperature either at the start of the
Occupied schedule or after the
Occupied schedule begins.
Default:
off
Note:
Progressive recovery is
disabled if either DI1 or DI2 is
configured as remote NSB.
(on):
Enabled (provides the desired occupied temperature at the
start of the Occupied schedule)
(off):
Disabled (provides the desired occupied temperature after the
Occupied schedule begins)
Table 2: Installer Configuration Menu (Part 5 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options