Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 7
states. The occupancy sensor can be
a room occupancy sensor or another
kind of occupancy detection (such as
a duct pressure switch*). Without an
occupancy sensor, the controller will
always be in Occupied mode.
occupancy sensor (wired to IN2 and
ICOM2 on the controller) can be used
to temporarily set the VAV box to
Standby mode when occupancy is not
sensed.
*An optional factory provided occupancy pressure switch is available for standalone fan powered terminal units to
determine occupancy by measuring duct pressure to determine whether the air handler is on (zone is occupied) or off
(zone is unoccupied).
Control Sequences
VAV boxes with Smart Equipment Controls will be factory mounted and wired according to the selected control sequence.
Links to each individual control submittal are shown below:
Table 2: Control Sequences
Smart Equipment Controls - Control Sequences
Description
Single Duct
Series Fan Powered Parallel Fan Powered
ZEC500 ZEC510
ZEC500
ZEC510
ZEC500
ZEC510
Cooling Only
6101
7101
6201
7201
6301
7301
1-Stage Electric Heat
6102
7102
6202
7202
6302
7302
2-Stage Electric Heat
6103
7103
6203
7203
6303
7303
3-Stage Electric Heat
6104
7104
6204
7204
6304
7304
Proportional Electric Heat
6105
7105
6205
7205
6305
7305
On/Off Hot Water Heat
6106
7106
6206
7206
6306
7306
Floating Hot Water Heat
6107
7107
6207
7207
6307
7307
Proportional Hot Water Heat
6108
7108
6208
7208
6308
7308
Supplemental Heat
6109
7109
6209
7209
6309
7309
Controller Parameters
Parameter Descriptions
This section provides information on the SE-ZEC Controller Parameters.
Static Parameters (All Applications)
The list of available SE-ZEC Controller Parameters changes depending on the application type that is selected
(Staged/Incremental/SCR). Table 2 shows the SE-ZEC Controller parameters that are available for every application
(Staged/Incremental/SCR).
Table 3: Default SE-ZEC Controller Parameters
Menu 1
Menu 2
Parameter Name Parameter Description
Parameter Values
Home Page
Setup
Active Baud Rate
Displays the active baud rate used for network
communication.
Read Only