Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 17
4.
Log in to the MAP Gateway
a.
Log in to the MAP Gateway using the default Admin login credentials found in the
MAP Gateway Quick
Start Guide
that is provided with the MAP Gateway (Part No. 24-10737-16)
5.
Change Passwords
a.
The first time you log in to the MAP Gateway, the Change Password and Passphrase web page appears.
You must change the Admin password and Wi-Fi passphrase.
After you change the Wi-Fi passphrase or
SSID, the web server restarts and you must rejoin the MAP Gateway Wi-Fi network using the new
passphrase. On some mobile devices, you must select and forget the original MAP Gateway Wi-Fi
network before rejoining the network with the new passphrase.
6.
Use the MAP Gateway
a.
Select a device from the equipment list and use the web pages from the MAP Gateway to view,
commission and configure devices as needed.
For more information on the MAP Gateway reference the following Johnson Controls documents:
VAV Handheld Balancing Tool
A Handheld Balancing Tool (Part # 15037701) can be used to aid in balancing units with SE-ZEC Controllers.
1.
Connect the VAV Balancing Tool to the Network Zone Sensor associated with the controller you want to balance.
2.
Press and hold the Enter and Cancel buttons on the VAV Balancing Tool for 5 seconds to enter balancing mode.
3.
Balance the unit. Reference the Metasys Balancing Sensor User Guide that comes with the VAV Handheld
Balancing Tool.
Parameters that can be balanced include:
Cooling Max Flow [CMAX]
Cooling Min Flow [CMIN]
Heating Flow [HTG]
Differential Flow [DIFF]
Box Area [AREA]
Pickup Gain – K Factor [K]
dP Offset [DPO]
4.
To Exit, Press the enter button when Exit appears on the screen at the highest sub menu.
For more information on the VAV Handheld Balancing Tool reference the following Johnson Controls documents:
Troubleshooting
Use the following information to troubleshoot the SE-ZEC Controllers. *NOTE: Please use the appropriate personal
protective equipment when troubleshooting.