Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 10
Menu 1
Menu 2
Parameter Name Parameter Description
Parameter Values
Home Page
Setpoints
Effective Heating
Setpoint
Effective Heating Setpoint
Read Only
Home Page
Setpoints
Occupied Cooling
Setpoint
When occupied the thermostat controls cooling to
this level. Set above Occupied Heating Setpoint.
Defaults to 72°F.
Adjustable:
46°F to 99°F
Home Page
Setpoints
Occupied Heating
Setpoint
When occupied the thermostat controls heating to
this level. Set below Occupied Cooling Setpoint.
Defaults to 68°F.
Adjustable:
45°F to 98°F
Home Page
Setpoints
Standby Cooling
Setpoint
In order for the Standby Cooling Setpoint to
appear, set the Occupancy Schedule to external.
When set to external the zone switches to this
setpoint when motion is no longer sensed and the
unit is occupied. Defaults to 74°F.
Adjustable:
46°F to 99°F
Home Page
Setpoints
Standby Heating
Setpoint
In order for the Standby Heating Setpoint to
appear, set the Occupancy Schedule to external.
When set to external, the zone switches to this
setpoint when motion is no longer sensed and the
unit is occupied. Defaults to 66°F.
Adjustable:
45°F to 98°F
Home Page
Setpoints
Unoccupied
Cooling Setpoint
When unoccupied the thermostat controls cooling
to this level. Defaults to 80°F.
Adjustable:
46°F to 99°F
Home Page
Setpoints
Unoccupied
Heating Setpoint
When unoccupied the thermostat controls heating
to this level. Set below Unoccupied Cooling
Setpoint. Defaults to 60°F.
Adjustable:
45°F to 98°F
Home Page
Setpoints
Warmer/Cooler
Adjust Range
This is the range that the warmer cooler
adjustment on the sensor can affect the setpoint.
Setting it to zero (0) means the user has no
adjustment at the sensor. Defaults to 5°F.
Adjustable:
0°F to 5°F
Home Page
Setpoints
Warmup
Differential
Sets the required differential between the supply
air temperature (SAT) sensor and the zone
temperature (ZNT) sensor in occupied mode to
notify the controller that warmup conditions are
present. When warmup conditions are present the
minimum supply airflow will be set to Warmup Min
Flow.
Home Page
Commissioning
Cooling Max Flow
Sets the maximum supply air flow of the VAV box
when cooling.
Adjustable:
0 cfm to 10000 cfm
Home Page
Commissioning
Occupied Cooling
Min Flow
Sets the minimum supply air flow of the VAV box
when cooling.
Adjustable:
0 cfm to 10000 cfm
Home Page
Commissioning
Occupied Heating
Min Flow
Sets the minimum supply air flow of the VAV box
when heating. Note: When the zone is in heating
mode, the supply air flow is constant. Thus, no
maximum heating air flow. This value must
exceed Staged Device Min Flow to allow electric
heat to energize.
Adjustable:
0 cfm to 10000 cfm
Home Page
Commissioning
Staged Device
Min Flow
Sets the minimum heating flow for electric reheat
control. This parameter serves an additional
control safety to the high-limit switches in the box.
It is best practice to set this parameter to 70 cfm
per kW of electric heat.
Adjustable:
0 cfm to 10000 cfm
Home Page
Commissioning
Unoccupied
Cooling Min Flow
Sets the minimum supply air flow of the VAV box
when unoccupied cooling and in the cooling
mode.
Adjustable:
0 cfm to 10000 cfm