Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
96/168
008831 en 2020.10
6.13
Noise data
Noise data is stated in:
SWL
: A-weighted
s
ound po
w
er
l
evel
SPL
: A-weighted
s
ound
p
ressure
l
evel, in free field over reflecting plane (1 m distance).
•
Noise data is based on measurements according to ISO 9614-2.
•
The stated SPL values are calculated using the formula 8.3 in ISO 3744.
•
The stated values are for a complete unit operating in 100% capacity.
6.14
Noise data for SAB 193-233-283
Evaporating temperature, TE
-15°C
Condensing temperature, TC
+35°C
Refrigerant
R717/HCFC/HFC
Speed
2950 rpm
For 60 Hz-driven compressors, add + 2 dBA to the stated levels.
Type of unit
SWL
SPL
SAB 193 S
103
84
SAB 193 L
104
84
SAB 233 S
105
86
SAB 233 L
106
86
SAB 233 E
107
86
SAB 283 S
106
88
SAB 283 L
107
88
SAB 283 E
108
88
SAB 283 X
108
88
Table 24: Noise data
Noise data for other operating conditions can be provided by Johnson Controls Denmark on
request.
Note:
•
The actual SPL value on site will be between the stated SPL and SWL depending on the
acoustic environment in the machine room.
•
In a typical machine room without any noise absorbing materials, the actual SPL will be
approximately 14 dBA higher than the stated SPL (free field value).
•
Checking the actual SPL must therefore always be accompanied by measurements of the
acoustic environment of the machine room. Alternatively, ISO 9614-2 could be followed
at the installation site to obtain SWL comparable values.
•
Be aware of local/national requirements for the use of ear protection. Generally, it is rec-
ommended to use ear protection in machine rooms.
Summary of Contents for Sabroe SAB 193 L
Page 1: ...SAB 193 233 283 S A frame including ATEX Screw compressor units Engineering manual en ...
Page 2: ......
Page 169: ......