PEAK® OEM 18 240 Volt SMART Equipment Controller Installation Instructions
2
North American Emissions Compliance
United States
Canada
Installation
Observe these guidelines when installing a PEAK OEM 18 240 Volt controller
:
•
Transport the controller in the original container to minimize vibration and shock damage.
•
Verify that all parts shipped with the controller.
•
Do not drop the controller or subject it to physical shock.
Parts Included
•
one PEAK OEM 18 240 Volt SMART Equipment controller
•
one installation instructions sheet
Materials and Special Tools Needed
•
three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
•
one 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
•
small straight-blade screwdriver for securing wires in the terminal blocks
Mounting
Observe these guidelines when mounting a field controller:
•
Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
•
Mount the controller horizontally on 35 mm DIN rail whenever possible.
•
Mount the controller in the proper mounting position (Figure 1).
•
Use shims or washers to mount the controller securely and evenly on the mounting surface.
•
Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements
•
Provide for sufficient space around the controller for cable and wire connections for easy cover removal and
good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
•
Do not mount the controller on surfaces prone to vibration, such as duct work.
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area may
cause harmful interference, in which case users will be required to correct the interference at their own expense.
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
IMPORTANT:
Only qualified personnel should install or service PEAK products. These instructions are a guide
for such personnel. Mount the PEAK controllers on a wall or DIN rail inside an enclosure (rated at least IP20).
Carefully follow all instructions in this document and all instructions for the controller.