PEAK® OEM 18 240 Volt SMART Equipment Controller Installation Instructions

19

SA/FC Bus and Supply Power Wiring Guidelines

Table 5 provides information about the functions, ratings,  and requirements for the communication bus and supply 
power terminals; and guidelines for wire sizes, cable types, and cable lengths when wiring the controller's 
communication buses and supply power. 

In addition to the guidelines in Table 5, observe these  guidelines when wiring an SA or FC bus and the 120/240 VAC 
supply power:

Run all low-voltage wiring and cables separate from high-voltage wiring.

All SA and FC bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.

Shielded cable is strongly recommended for all SA and FC bus cables.

Refer to the 

MS/TP Communications Bus Technical  Bulletin (LIT-12011034) 

for detailed information  regarding 

wire size and cable length requirements for  the SA and FC buses.

Refer to the 

N2 Communications Bus Technical  Bulletin (LIT-636018) 

for detailed information regarding wire 

size and cable length requirements for  the N2 bus. 

Table 5:  Communication Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and 

Cables (Part 1 of 2)

Terminal 
Block/Port 
Label

Terminal Labels

Function, Electrical Ratings/Requirements

Recommended Cable Type

120/240 
VAC 
~INPUT

L

120/240 VAC Power Supply - Hot
120/240 VAC, 50/60 Hz

The power supply quick disconnects 
can accommodate the following 
maximum wire sizes:

• 

two wires per terminal: 1.5 mm

2

18 AWG maximum

• 

one wire per terminal: 2.5 mm

2

12 AWG maximum

Note:

Determine the required wire 

size for the line voltage input power 
terminals according to the controller 
operational VA specification and the 
local, regional, or national, electric 
codes.

N

120/240 VAC Power Supply - Neutral
120/240 VAC, 50/60 Hz
20 VA

Functional Earth

FC BUS/
SA BUS
FC BUS 
(Upper)

+

FC Bus Communication

0.6 mm (22 AWG) stranded, 3-wire 
twisted, shielded cable recommended

-

COM

Signal Reference (Common) for Bus 
communications

SHD

Isolated terminal (optional shield drain 
connection)

SA BUS
(Port)

SA BUS

RJ-12 6-Position Modular Connector provides: 
SA Bus Communications SA Bus Signal 
Reference and 15 VDC Common
15 VDC, 71.5 ohms at 4 W, Power for Bluetooth 
Commissioning Converter or ZFR1811 Wireless 
Router

24 AWG 3-pair CAT3 Cable <30.5 m 
(100 ft)

FC BUS/
SA BUS
SA BUS
(Lower)

+

SA Bus Signal Reference and 15 VDC Common

0.6 mm (22 AWG) stranded, 4-wire 
(2 twisted pairs), shielded cable 
recommended

Note:

The + and - wire are one 

twisted pair, and the COM and SA 
PWR are the second twisted pair of 
wires.

-

COM

SA Bus Communications

PWR

15 VDC Supply Power for Devices on the SA Bus 
(Maximum total current draw for SA bus is 240 
mA)

Summary of Contents for PEAK OEM 18

Page 1: ... local display built in BACnet schedule objects and calendars Mobile Access Portal MAP compatibility for configuration through smart mobile devices and remote connectivity multi protocol support for BMS integration BACnet MS TP N2 and Modbus RTU through on board display dedicated SA bus for Johnson Controls smart end devices dedicated Modbus port for third party end device integration Modbus Maste...

Page 2: ...quirements Provide for sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller 50 mm 2 in minimum on the top bottom and front of the controller Do not mount the controller on surfaces prone to vibration such as duct work This equipment has been tested and found to comply with the limits for a Class A digital device pu...

Page 3: ...1 PEAK OEM 18 240 Volt Controller Mounting Position DIN Rail Mount Applications Mounting the field controller horizontal on 35 mm DIN rail is the preferred mounting method To mount a field controller on 35 mm DIN rail 1 Securely mount a 20 cm 8 in or longer section of 35 mm DIN rail horizontal and centered in the desired space so that the controller mounts in the horizontal position shown in Figur...

Page 4: ...may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death Risque de décharge électrique Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique Plusieurs isolations et débranchements sont peut être nécessaires pour couper entièrement l alimentation de ...

Page 5: ...d in Table 3 use the appropriate gauge wiring For all the spade terminals used for this application follow the guidelines in Table 3 and use a spade connector with screw terminals Figure 3 PEAK OEM Controller Spade Terminals Field Wiring For all I O terminals listed in Table 3 use the appropriate gauge wiring For all the spade terminals used in this application follow the guidelines in Table 3 and...

Page 6: ...cate as a slave mode and connect to the Modbus network which consists of a Master Modbus device Due to the OEM application dynamics of the PEAK controllers the Modbus resistor table is not based on a default application For each new application a new Modbus table is generated as part of the OEM application development The PEAK support team identifies the configuration and application for Modbus Th...

Page 7: ...ontact Rated up to 240 VAC 5 Mounting clips three 6 Three Configurable Outputs CO terminal blocks Voltage Analog Output 0 to 10 VDC 10 mA Binary Triac Outputs 24 VAC Externally Sourced See Table 3 7 USB Host Port 8 Cover Lift Tabs 9 Sensor Actuator SA Bus Port RJ 12 6 pin Modular Jack See SA Bus Port section 10 LED Status Indicators See Table 7 11 Four Keypad buttons 12 Display with backlight Stra...

Page 8: ...lancing Tool specified network sensors or other SA Bus devices with RJ 12 plugs 13 Four Binary Inputs BI Terminal blocks Dry contact maintained or pulse counter accumulator mode See Table 3 14 Five Universal Inputs UI Terminal blocks Voltage Analog Input 0 10VDC Current Analog Input 4 20mA Resistive Analog Inputs 0 to 600K Ohms or Dry Contact Binary Input See Table 3 15 Stacked Connector Field Con...

Page 9: ...h may consist of one to many slave Modbus devices Each Modbus slave device has a unique Modbus Register table and must be configured within the application of the PEAK controller The configuration and application of Modbus is identified by the PEAK support team and programmed based on OEM applications Figure 10 Modbus Terminal Block Supply Power Terminal Block The 120 240 VAC supply power terminal...

Page 10: ...oes not have an integral EOL termination feature The EOL terminator is a compact lightweight module wrapped in a protective cover that you can quickly install in a variety of ways The EOL connects directly to the terminating device on a bus segment with the attached wire leads The EOL requires 24 VAC Class 2 power which is supplied by the field device or another 24 VAC source SUPPLY POWER SPADE TE...

Page 11: ...tion Details Part 1 of 5 Type of Field Device Type of Input Output Termination Diagrams Resistive Input RTD Monitor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI Current Input External Source Isolated UI RTD Temperature Element Controller IN ICOM FIELD DEVICE OUT COM POWER SUPPLY Controller IN ICOM Controller IN ICOM 15V FIELD DEVICE VDC Control...

Page 12: ...ck from EPP 100 UI Dry Contact Binary Input UI BI Table 2 Termination Details Part 2 of 5 Type of Field Device Type of Input Output Termination Diagrams Controller FIELD DEVICE VDC Output 15V IN IN ICOM FIELD DEVICE VDC 15V Controller IN ICOM FIELD DEVICE Power Supply ICOM IN 15V EPP 1000 Retracted Stroked Wh Vio Wh Org Wh Bm Controller FIELD DEVICE ICOM IN DRY CONTACT N O N C or as required Contr...

Page 13: ...nal Block 1 1 2 3 4 5 6 OCOM OUT Controller 24 VAC COM 24 VAC HOT Common Power Calibration Output Current Input Voltage Input Feedback Terminal Block 1 1 2 3 4 5 6 OCOM OUT Controller 24 VAC Com 24 VAC Hot Add Jumper from 24 VAC COM to only one AO COM per Transformer Common Power Calibration Output Current Input Voltage Input Feedback Terminal Block 1 1 2 3 4 5 6 OCOM OUT Controller 24 VAC Com 24 ...

Page 14: ...utput BO Table 2 Termination Details Part 4 of 5 Type of Field Device Type of Input Output Termination Diagrams 24 VAC Load OUTn A OUTn B Controller Field Devices Note Rated load of 0 5 resistive Amps max COM 240VAC Load OUTn A OUTn B CONTROLLER COM Note Rated loads per Table Refer Binary Output Relays FIELD DEVICE ...

Page 15: ...s of wire size or number of wires should consist of stranded insulated and twisted copper wires Shielded cable is not required for input or output cables Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs outputs with cables less than 30 m 100 ft typically do not require an offset in the software setup Cable runs over ...

Page 16: ... INn INn Analog Input Voltage Mode 0 10 VDC 10 VDC maximum input voltage Internal 67k ohm Pull down See Guideline A in Table 4 Analog Input Current Mode 4 20 mA Internal 100 ohm load impedance See Guideline B in Table 4 Analog Input Resistive Mode 0 600k ohm Internal 12 V 15k ohm pull up Qualified Sensors 0 2k ohm potentiometer RTD 1k Nickel Johnson Controls sensor 1k Platinum and A99B Silicon Tem...

Page 17: ...F 100K cycles The RELAY output terminals can accommodate the following maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum or One wire per terminal 2 5 mm2 maximum 12 AWG or 2 16 AWG Note You must determine the required wire size for the high voltage 30 V terminals according to relay ratings the applied load and the local national or regional electrical codes Maximum loads stated requ...

Page 18: ...wisted wire 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire N A 24 AWG stranded copper 107 m 350 ft twisted wire B 1 5 mm2 18 AWG stranded copper 229 m 750 ft twis...

Page 19: ...Function Electrical Ratings Requirements Recommended Cable Type 120 240 VAC INPUT L 120 240 VAC Power Supply Hot 120 240 VAC 50 60 Hz The power supply quick disconnects can accommodate the following maximum wire sizes two wires per terminal 1 5 mm2 18 AWG maximum one wire per terminal 2 5 mm2 12 AWG maximum Note Determine the required wire size for the line voltage input power terminals according ...

Page 20: ...WG 2 wire COM 24 VAC Power Supply Common MOD BUS Modbus communications 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended COM Signal Reference Common for bus communications Table 6 SA Bus Device Address Description Device Address Use on Description 0 Switch 128 Off Reserved for FC Bus Supervisory Controller not for use on field controllers 1 to 3 Switch 128 Off Reserved for p...

Page 21: ...Check Output wiring for short circuits and cycle power to the controller On Steady Power Connected FAULT Red Off Steady Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode or a firmware mismatch exists between the PEAK OEM and the ZRF1811 Wireless Field Bus Router Blink 2 Hz Download or Startup in progress not ready for normal...

Page 22: ...Modbus communication half duplex Master RTU port Processor RX631 Renesas 32 bit microcontroller Memory 16 MB flash memory and 8 MB RAM Input and Output Capabilities Five Universal Inputs User Configurable 3 available modes Voltage Input 0 to 10 VDC Current Sense Input 4 to 20 mA Resistive Inputs Dry Contact Inputs Four Binary Inputs Defined as Dry Contact maintained or Pulse Counter Accumulator Mo...

Page 23: ... to CRF47 Part 15 Subpart B Class A Canada UL Listed File E107041 CNN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that this product is also in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive Declared as Electronic Independently mounted control suitable for DIN...

Reviews: