5750156-UIM-B-0919
12
Johnson Controls Ducted Systems
1. Airflow tested with dry coil conditions, without air filters, at 230 V.
2. Applications above 0.8 in. W.C. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data result from operating at 208 V. Data above may be used in those cases.
5. Heating applications tested at 0.50 in. W.C. esp, and cooling applications tested at 0.30 in. W.C. esp per standards.
PCG4A42075
Low (1)
1315
1266
1229
1194
1156
1117
1080
1036
948
Low/Medium (2)
1436
1382
1342
1304
1262
1220
1179
1131
1035
Medium (3)
1458
1406
1365
1327
1286
1244
1203
1155
1059
Medium/High (4)
1573
1523
1484
1445
1408
1367
1327
1279
1183
High (5)
1966
1914
1862
1810
1757
1705
1653
1600
1496
PCG4A42100
Low (1)
1436
1382
1342
1304
1262
1220
1179
1131
1035
Low/Medium (2)
1544
1492
1455
1416
1376
1336
1294
1248
1156
Medium (3)
1573
1523
1484
1445
1408
1367
1327
1279
1183
Medium/High (4)
1681
1640
1599
1557
1517
1478
1436
1393
1307
High (5)
1935
1887
1834
1788
1743
1701
1651
1591
1471
PCG4B48065
Low (1)
1046
1009
980
946
915
878
844
779
649
Low/Medium (2)
1295
1250
1213
1172
1133
1087
1045
964
802
Medium (3)
1620
1564
1517
1466
1418
1360
1308
1206
1002
Medium/High (4)
1798
1722
1669
1620
1572
1527
1480
1413
1280
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
1609
PCG4B48100
Low (1)
1620
1564
1517
1466
1418
1360
1308
1206
1002
Low/Medium (2)
1694
1630
1580
1530
1482
1430
1380
1292
1116
Medium (3)
1798
1722
1669
1620
1572
1527
1480
1413
1280
Medium/High (4)
1835
1758
1703
1653
1604
1558
1511
1442
1304
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
1609
PCG4B48125
Low (1)
1620
1564
1517
1466
1418
1360
1308
1206
1002
Low/Medium (2)
1798
1722
1669
1620
1572
1527
1480
1413
1280
Medium (3)
1922
1863
1804
1754
1724
1658
1612
1559
1453
Medium/High (4)
2001
1952
1890
1839
1820
1742
1696
1651
1561
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
1609
PCG4B60065
Low (1)
1073
1043
1009
988
963
941
917
892
842
Low/Medium (2)
1329
1292
1250
1223
1192
1165
1136
1105
1043
Medium (3)
2054
1998
1934
1890
1843
1801
1757
1710
1616
Medium/High (4)
2195
2144
2098
2049
2003
1955
1883
1868
1838
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
1973
PCG4B60100
Low (1)
1730
1682
1628
1592
1552
1517
1479
1439
1359
Low/Medium (2)
1858
1807
1749
1710
1667
1629
1589
1546
1460
Medium (3)
2054
1998
1934
1890
1843
1801
1757
1710
1616
Medium/High (4)
2195
2144
2098
2049
2003
1955
1883
1868
1838
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
1973
PCG4B60125
Low (1)
2063
2008
1943
1899
1851
1809
1763
1717
1625
Low/Medium (2)
2130
2084
2032
1983
1927
1951
1860
1815
1725
Medium (3)
2195
2144
2098
2049
2003
1955
1883
1868
1838
Medium/High (4)
2275
2252
2169
2154
2112
2065
1989
1976
1950
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
1973
Table 13:
Airflow Performance - Side Duct Application (Continued)
Model
Motor Speed
External Static Pressure (in. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.0
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM