Installation Guide
FCU Controller
20
INPUT 6 (I6) - EMERGENCY SHUTDOWN
Input must be wired to the Emergency Shutdown. Wiring for the I6 is shown
in Figure 13. To wire I6 to a dry contact:
1
. Select the correct jumper setting for a dry contact on
J4
.
2
. Connect one lead of the normally open dry contact to input terminal
I6
on terminal block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
J9
J4
J4
J5
J6
J7
J8
J9
GND I5
I4 GND I3
I2
VOUT
I1
GND
I6
J2
DRY CONTACT
Figure 13. I6 - Dry Contact Wiring.