FCU Controller Installation
Guide
19
INPUT 5 (I5) - FAN STATUS
Input 5 must be wired to the Fan Status. Wiring for the I5 is shown in Figure
12. To wire I5 to a dry contact:
1
. Select the correct jumper setting for a dry contact on
J5
.
2
. Connect one lead of the normally open dry contact to input terminal
I5
on terminal block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
J9
J5
J4
J5
J6
J7
J8
J9
J2
DRY CONTACT
GND I5
I4 GND I3
I2
VOUT
I1
GND
I6
Figure 12. I5 - Dry Contact Wiring.