FCU Controller Installation
Guide
15
INPUT 1 (I1) - DISCHARGE AIR TEMPERATURE WIRING
Input 1 must be wired to the Discharge Air Temperature. Wiring for I1 is
shown in Figure 8. To wire I1 to a thermistor:
1
. Select the correct jumper setting for a thermistor on
J9
.
2
. Connect one lead of the thermistor to input terminal
I1
on terminal
block
J2
.
3
. Connect the other lead to one of the
GND
terminals.
NOTE:
Only a 10K Type II (CP Curve) thermistor may be used.
J9
J9
J4
J5
J6
J7
J8
J9
J2
THERMISTOR
GND I5
I4 GND I3 I2
VOUT
I1
GND
I6
Figure 8. I1 - Thermistor Wiring.