
Table 9: Dual trunk options
Trunk type
Supported dual trunk application
1 RS232 Modbus
1 TCP M-Bus
1 RS232 M-Bus
1 TCP Modbus
Modbus and M-Bus
1 TCP Modbus
1 TCP M-Bus
Wiring
Important:
Do not connect 24 VAC supply power to the NCE before finishing wiring and
checking all wiring connections. Short circuits or improperly connected wires may result in
permanent damage to the equipment.
Important:
• Use copper conductors only. Make all wiring in accordance with local, national, and regional
regulations. The NCE is a low-voltage device (<30 VAC) in North America and an extra low-
voltage device in Europe. Do not exceed the NCE electrical ratings.
• Do not remove the terminal block keys. The terminal block plugs and the terminal sockets
are keyed to fit together in the correct configuration only.
• Prevent any static electric discharge to the NCE. Static electric discharge can damage the
NCE and void any warranties.
• Ensure the network and field bus wiring meets the specifications, rules, and guidelines in
the
Power supply, network, and communication connections
section in this document.
Mount the network engine securely before wiring.
Follow these guidelines when wiring a network engine:
• Route the supply power wires and communication cables at least 50 mm (2 in.) away from the
vent slots on the sides of the network engine housing.
• Provide slack in the wires and cables. Keep cables routed neatly around the network engine to
promote good ventilation, LED visibility, and ease of service.
Wiring for N2, MS/TP, or Modbus RTU Protocol
1. Connect the Ethernet cable to the RJ-45, 8-pin Ethernet port as shown in
NCE25 physical
features
.
2. Connect the BAS network cables to the appropriate ports.
3. For Modbus RTU protocol using the RS232C serial port, use a cable to connect the RS-232/
RS-485 converter to the RS232C serial port on the network engine.
Note:
The maximum cable length between devices connected though an RS-232 line
depends on the baud rate used. In general, at 9600 baud ensure the length does not
exceed 15 meters.
4. Wire from the RS-485 terminal on the converter to the RS-485 port on the vendor device. The
NCE25 Installation Instructions
14