M9102-xGA-xS / M9104-xGA-xS
2
Technical Specifications
M910x-xGA-1S
M910x-xGA-5S
Product Codes
M9102-AGA-1S
M9104-AGA-1S
M9102-IGA-1S
M9104-IGA-1S
M9104-GGA-1S
Power Requirements
AC 24 V +25% / -20% at 50/60 Hz
2.1 VA
2.5 VA
3.0 VA
3.6 VA
Safety Extra-Low Voltage (SELV) Class III
Control Type
Floating Control without Timeout
ON/OFF and Floating Control With Timeout
Modulating
Input Signal
AC 24 V +25% / -20% at 50/60 Hz, SELV Class III
DC 0(2) to 10 V or 0(4) to 20 mA
with field furnished 500 ohm resistor
---
with Timeout
Feedback Signal
---
---
DC 0(2)...10 V Corresponds to input
span selection (DC 10V at 1 mA)
Motor Input Impedance
200 ohms Nominal
Running Torque
2 Nm
4 Nm
2 Nm
4 Nm
4 Nm
Travel Time
(for 90° of Rotation)
30 Seconds at 60 Hz
36 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
30 Seconds at 60 Hz
36 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
Rotation Range
91° ±2°, CW or CCW
Cycles
100,000 Full Stroke Cycles;
2,500,000 Repositions at Rated Running Torque
Audible Noise Rating
35 dBA Nominal at 1 m
Electrical Connections
1.2 m Polyvinyl Chloride (PVC) cable with 0.75 mm
2
conductors and 6 mm ferrule ends
Mechanical Connections
Up to13 mm Diameter Round Damper Shafts, or 10 mm Square Damper Shafts
Enclosure
NEMA 2, IP 42
Ambient Conditions
- Operating
-20 to 60° C; 90% RH Maximum, Noncondensing
- Storage
-29 to 66° C; 90% RH Maximum, Noncondensing
Shipping Weight
0.5 Kg
Compliance
- North America
UL Listed, File E27734, CCN XAPX (United States) and XAPX7 (Canada) - Actuator Housing is Plenum Rated per CSA C22.2 No. 236/UL 1995, Heating and Cooling Equipment
- European Union
CE Mark, EMC Directive 89/336/EEC
- Australia and New Zealand
C-Tick Mark, Australia / NZ Emissions Compliant
Product Codes
M9102-AGA-5S
M9104-AGA-5S
M9102-IGA-5S
M9104-IGA-5S
M9104-GGA-5S
Power Requirements
AC 24 V +25% / -20% at 50/60 Hz
2.1 VA
2.5 VA
3.0 VA
3.6 VA
Safety Extra-Low Voltage (SELV) Class III
Control Type
Floating Control without Timeout
ON/OFF and Floating Control With Timeout
Modulating
Input Signal
AC 24 V +25% / -20% at 50/60 Hz, SELV Class III
DC 0(2) to 10 V or 0(4) to 20 mA
with field furnished 500 ohm resistor
---
with Timeout
Feedback Signal
---
---
---
Motor Input Impedance
200 ohms Nominal
Running Torque
2 Nm
4 Nm
2 Nm
4 Nm
4 Nm
Travel Time
(for 90° of Rotation)
30 Seconds at 60 Hz
36 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
30 Seconds at 60 Hz
36 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
Rotation Range
91° ±2°, CW or CCW
Cycles
100,000 Full Stroke Cycles;
2,500,000 Repositions at Rated Running Torque
Audible Noise Rating
35 dBA Nominal at 1 m
Electrical Connections
M3 Screw Terminals
Mechanical Connections
Up to13 mm Diameter Round Damper Shafts, or 10 mm Square Damper Shafts
Enclosure
NEMA 1, IP 40
Ambient Conditions
- Operating
-20 to 60° C; 90% RH Maximum, Noncondensing
- Storage
-29 to 66° C; 90% RH Maximum, Noncondensing
Shipping Weight
0.5 Kg
Compliance
- North America
UL Listed, File E27734, CCN XAPX (United States) and XAPX7 (Canada) - Actuator Housing is Plenum Rated per CSA C22.2 No. 236/UL 1995, Heating and Cooling Equipment
- European Union
CE Mark, EMC Directive 89/336/EEC
- Australia and New Zealand
C-Tick Mark, Australia / NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting
from misapplication or misuse of its products.