LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions
6
Wiring Resistive Inputs
Use this input configuration to monitor 100k ohm RTDs, 10k ohm Type 2 and Type 3 thermistors, and
potentiometers (Figure 6 and Figure 7).
Note:
The Application Specific Controllers do not support 100 or 1,000 ohm inputs.
Note:
example, an 18 AWG wire, 25 feet long (7.6 m) can create an offset of 2°F (1.1°C).
Figure 6: Resistive Input – RTD/Thermistor
Figure 7: Resistive Input – 10k Ohm