![Johnson Controls LN Series Installation Instructions Manual Download Page 19](http://html.mh-extra.com/html/johnson-controls/ln-series/ln-series_installation-instructions-manual_2023101019.webp)
LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions
19
Inputs
Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact; 500 milliseconds minimum ON/OF
Voltage: 0 to 10 VDC,
Current: 4 to 20 mA with 249 ohms
external resistor (wired in parallel)
Resistor Support:
Thermistor: Type 2 and Type 3 10k ohms (10k ohms at 25
°
C [77
°
F])
Range: -40 to 150
°
C (-40
to 302
°
F)
Platinum:
PT1000: 1k ohm (1k ohms at 0°C [32°F])
Range: -40 to 150
°
C (-40
to 302
°
F)
PT100: 100 ohms (100 ohms at 0°C [32°F])
Range: -40 to 135
°
C (-40
to 275
°
F)
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
Range: -40 to 150
°
C (-40
to 302
°
F)
Potentiometer:
Translation table configurable on several points
Input Resolution:
16-bit analog/digital converter
Outputs
Digital:
24 VAC Triac, digital (on/off), PWM, or floating
software configurable
0.5 A continuous
1.0 A at 15% duty cycle for a 10-minute period
PWM control:
adjustable period from 2 seconds to 15 minutes
Floating control:
requires two consecutive output
minimum plus on/off: 500 milliseconds
adjustable drive time period
External or internal power supply (jumper selectable)
Universal:
0-10 VDC, digital 0-12 VDC (on/off), PWM, or floating
PWM control:
adjustable period from 2 seconds to 15 minutes
Floating control:
requires two consecutive outputs
minimum plus on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60
°
C [140
°
F])
minimum resistance 200 ohms
Auto reset fuse
60 mA at 60
°
C (140
°
F)
100 mA at 20
°
C (68
°
F)
Output Resolution:
10-bit digital/analog converter
Electromagnetic
Compatibility
CE Emission:
EN61000-6-3: 2007 Generic standards for residential, commercial, and light-
industrial environments (pending).
CE Immunity:
EN61000-6-1: 2007; Generic standards for residential, commercial, and light-
industrial environments (pending).
FCC:
This device complies with FCC rules part 15, subpart B, class B
Compliance
UL Listed:
UL916 Energy management equipment
Material
1
:
UL94-5VA
UL Listed:
UL916 Energy management equipment
Material
UL94-5VA
1.
All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste
Electrical and Electronic Equipment (WEEE) directive.
Table 6: LN-PRG203-2 Programmable Controller (Part 2 of 2)