Installation Instructions
LC-200/BLC-200
2
3. CONNECTION AND SETUP
Dip
PULSE
--> off = 1 pulse - on = 2 pulses
Dip
RANGE
--> off = 7m - on = 15m range
Dip
LED
--> off = led off - on = led on
Jumpers
T
-
A
-
EOL
open = NC contacts without resistors (not for UL/ULC applications)
Jumpers
T
-
A
-
EOL
closed = DEOL supervision with internal resistors
SUPPLY: power supply 9-15 VDC / 25 mA.
Note:
For UL/ULC installations the detector shall be provided with minimum of 4 hours of standby power from either
a listed compatible control unit or power supply. Use only resistive loads on the outputs.
Installation must be carried out by trained personnel according to professional standards.
The manufacturer accepts no responsibility if the product is tampered with by unauthorized persons.
The alarm system should be checked for proper operation at least once a month. However, a reliable electronic alarm system does not prevent
intrusion, robbery, fire or anything else but merely decreases the risk of such situations occurring.
LC-200/BLC-200 complies with requirements EN 50131-2-2 Grade 2, EN 50131-2-2 Class II
Technical Characteristics
RANGE
15 m
HORIZONTAL COVERAGE
100°
LENSES
LODIFF
®
Fresnel Lens
POLY IR
®
4 material
LED
blue
ALARM DURATION
2 s
SELF-DIAGNOSTICS
-
LED WALK TEST
YES
MICROWAVE FREQUENCY
-
SOLID STATE RELAY
YES
EOL RESISTANCE
YES
CREEP ZONE DEVICE
YES
CASE TAMPER
YES
BACK TAMPER
YES
ANTI-MASKING
-
PULSE COUNTER
YES
RFI PROTECTION
30 V/m
HEAT COMPENSATION
YES
FULLY DIGITAL
YES
SWIVEL OPTION
YES
POWER SUPPLY
9-15 VDC / 25 mA
COVER MATERIAL
ABS
PET IMMUNITY
YES
OPERATING TEMPERATURE
-10°C to +40°C
UL/ULC tested: 0°C to 49°C
HUMIDITY
93% RH
DIMENSIONS
114 x 63 x 40 mm
LC-200: DEOL supervision
(external resistors/
open jumpers)
NC (no EOL supervision/
open jumpers)
Not used on UL/ULC
listed installations
101W. MORNINGSIDE DR. FORT WORTH, TX 76110, U. S. A. (817) 926-7474, FAX:(817)926-7146
fresnel technologies inc.
2003
SIDE VIEW:
2.1m
(6.8ft)
TOP VIEW:
10m
(33ft)
(50ft)
15m
FRONT VIEW:
(50ft)
15m
5m
(16ft)
jay
WP 0.9 GI 6 T1
PET IMMUNE ARRAY
(28.2ft)
8.6m
(15.7ft)
4.8m
(6.8ft)
2.1m
35.6mm
(1.4 in)
49.8 mm
(1.96 in)
12.5 mm
(0.49 in)
95°
5m
(16ft)
10m
(33ft)
(50ft)
15m
0
Figure 7
101W. MORNINGSIDE DR. FORT WORTH, TX 76110, U. S. A. (817) 926-7474, FAX:(817)926-7146
fresnel technologies inc.
2003
SIDE VIEW:
2.1m
(6.8ft)
TOP VIEW:
10m
(33ft)
(50ft)
15m
FRONT VIEW:
(50ft)
15m
5m
(16ft)
jay
WP 0.9 GI 6 T1
PET IMMUNE ARRAY
(28.2ft)
8.6m
(15.7ft)
4.8m
(6.8ft)
2.1m
35.6mm
(1.4 in)
49.8 mm
(1.96 in)
12.5 mm
(0.49 in)
95°
5m
(16ft)
10m
(33ft)
(50ft)
15m
0
Figure 7
Zx COM
–
+
EOL
A
T
EOL
SUPPLY
ALARM
TAMPER
–
+
EOL
TAMPER
LC-200
All 3 jumpers open
Negative connected
tamper
5.6 kohm
5.6 kohm
Panel
COM Zx
–
+
EOL
A
T
EOL
SUPPLY
ALARM
TAMPER
–
+
EOL
TAMPER
BLC-200
All 3 jumpers open
Negative connected
10 kohm
10 kohm
tamper
Panel
Zx COM
–
+
EOL
A
T
EOL
SUPPLY
ALARM
TAMPER
–
+
EOL
TAMPER
LC-200/BLC-200
All 3 jumpers open
Negative connected
tamper
Panel
10m
(33ft)
5m
(16ft)
5m
(16ft)
10m
(33ft)
2.1m
(6.8ft)
2.1m
(6.8ft)
4.8m
(15.7ft)
8.6m
(28.2ft)
15m
(50ft)
SIDE VIEW:
0
DEOL supervision
(internal resistors/closed jumpers)
Zx COM
–
+
EOL
A
T
EOL
SUPPLY
ALARM
TAMPER
–
+
EOL
TAMPER
LC-200/BLC-200
COM
R1
R2
NC / NO
TAMPER
All 3 jumpers closed
Zone ok = R1
Zone in alarm = R1 + R2
Tamper zones = open or short circuit
Negative connected
tamper
Panel
LC-200: R1 = 5.6 kohm; R2 = 5.6 kohm
BLC-200: R1 = 5.0 kohm; R2 = 5.0 kohm
BLC-200: DEOL supervision
(external resistors/
open jumpers)