I n s t a l l a t i o n , O p e r a t i o n , M a i n t e n a n c e
30
W A T E R - S O U R C E H E A T P U M P S
JE-Series
I s s u e D a t e :
M a y 1 0 , 2 0 2 1
Blower Performance Data
Airflow in CFM with wet coil and clean air filter
Model Max ESP
(in wg)
Fan Motor
(hp)
Range
Cooling Mode Dehumid Mode Heating Mode Fan Only
Mode
Stg 2
Stg 1
Stg 2
Stg 1
Stg 2
Stg 1
026
1.0
1/2
Default
700
525
550
425
750
600
350
Maximum
1000
800
800
600
1000
850
1000
Minimum
600
450
550
400
600
450
300
038
0.9
1/2
Default
1050
800
850
650
1100
850
550
Maximum
1500
1100
1200
900
1500
1100
1500
Minimum
900
600
825
550
900
600
450
049
1.0
1
Default
1400
1050
1100
850
1500
1150
700
Maximum
2000
1500
1600
1200
2000
1500
2000
Minimum
1200
900
1100
825
1200
900
600
064
0.7
1
Default
1750
1300
1400
1050
1875
1450
875
Maximum
2300
1900
2000
1500
2300
1900
2300
Minimum
1500
1100
1375
1000
1500
1100
750
072
0.7
1
Default
1900
1450
1650
1250
2000
1650
950
Maximum
2300
2200
2000
1800
2300
2200
2300
Minimum
1800
1350
1650
1250
1800
1350
900
Airflow is controlled /- 5% up to Max ESP shown with wet coil and standard 1” fiberglass filter.
Condenser hot water reheat equipped units are factory set to operate in stage 2 airflow.
JE-Series with Condenser Hot Water Reheat
All JE units have an ECM fan motor. The small amount
of additional pressure drop of the condenser hot water
reheat coil causes the ECM motor to slightly increase
RPM to overcome the added pressure drop and maintain
selected CFM up to the maximum ESP.
Unit minimum operating temperature when in the
dehumidification or cooling mode is 65°F DB. Operation
below this minimum may result in nuisance faults.