I n s t a l l a t i o n , O p e r a t i o n , M a i n t e n a n c e
24
W A T E R - S O U R C E H E A T P U M P S
JE-Series
I s s u e D a t e :
M a y 1 0 , 2 0 2 1
Electrical – Line Voltage, Cont’d.
Standard Units, Units with Modulating Motorized Valve
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
RLA
LRA
Qty
026
G
208/230/60/1
197/252
11.7
58.3
1
3.9
15.6
18.5
30
E
265/60/1
239/292
9.1
54.0
1
3.2
12.3
14.6
20
H
208/230/60/3
197/252
6.5
55.4
1
3.9
10.4
12.0
15
*F
*460/60/3
414/506
3.5
28.0
1
3.2
6.7
7.6
15
038
G
208/230/60/1
197/252
15.3
83.0
1
3.9
19.2
23.0
35
E
265/60/1
239/292
13.0
72.0
1
3.2
16.2
19.5
30
H
208/230/60/3
197/252
11.6
73.0
1
3.9
15.5
18.4
30
*F
*460/60/3
414/506
5.7
38.0
1
3.2
8.9
10.3
15
049
G
208/230/60/1
197/252
21.2
104.0
1
6.9
28.1
33.4
50
E
265/60/1
239/292
16.0
109.7
1
6.0
22.0
26.0
40
H
208/230/60/3
197/252
14.0
83.1
1
6.9
20.9
24.4
35
*F
*460/60/3
414/506
6.4
41.0
1
6.0
12.4
14.0
20
064
G
208/230/60/1
197/252
27.1
152.9
1
6.9
34.0
40.8
60
E
265/60/1
239/292
22.4
130.0
1
6.0
28.4
34.0
50
H
208/230/60/3
197/252
16.5
110.0
1
6.9
23.4
27.5
40
*F
*460/60/3
414/506
7.2
52.0
1
6.0
13.2
15.0
20
072
G
208/230/60/1
197/252
29.7
179.2
1
6.9
36.6
44.0
70
H
208/230/60/3
197/252
17.6
136.0
1
6.9
24.5
28.9
45
*F
*460/60/3
414/506
8.5
66.1
1
6.0
14.5
16.6
25
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors require a four wire power supply with neutral. ECM motor is rated
265 vac and is wired between one hot leg and neutral.
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Internal
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
RLA
LRA
Qty
026
G
208/230/60/1
197/252
11.7
58.3
1
0.8
3.9
16.4
19.3
30
E
265/60/1
239/292
9.1
54.0
1
0.7
3.2
13.0
15.3
20
H
208/230/60/3
197/252
6.5
55.4
1
0.8
3.9
11.2
12.8
15
*F
*460/60/3
414/506
3.5
28.0
1
0.7
3.2
7.4
8.3
15
038
G
208/230/60/1
197/252
15.3
83.0
1
0.8
3.9
20.0
23.8
35
E
265/60/1
239/292
13.0
72.0
1
0.7
3.2
16.9
20.2
30
H
208/230/60/3
197/252
11.6
73.0
1
0.8
3.9
16.3
19.2
30
*F
*460/60/3
414/506
5.7
38.0
1
0.7
3.2
9.6
11.0
15
049
G
208/230/60/1
197/252
21.2
104.0
1
0.8
6.9
28.9
34.2
50
E
265/60/1
239/292
16.0
109.7
1
0.7
6.0
22.7
26.7
40
H
208/230/60/3
197/252
14.0
83.1
1
0.8
6.9
21.7
25.2
35
*F
*460/60/3
414/506
6.4
41.0
1
0.7
6.0
13.1
14.7
20
064
G
208/230/60/1
197/252
27.1
152.9
1
1.1
6.9
35.1
41.8
60
E
265/60/1
239/292
22.4
130.0
1
1.1
6.0
29.5
35.1
50
H
208/230/60/3
197/252
16.5
110.0
1
1.1
6.9
24.5
28.6
45
*F
*460/60/3
414/506
7.2
52.0
1
1.1
6.0
14.3
16.1
20
072
G
208/230/60/1
197/252
29.7
179.2
1
1.1
6.9
37.7
45.1
70
H
208/230/60/3
197/252
17.6
136.0
1
1.1
6.9
25.6
30.0
45
*F
*460/60/3
414/506
8.5
66.1
1
1.1
6.0
15.6
17.7
25
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/internal secondary circulators require a four wire power supply with neutral. ECM
motors/Condenser Hot Water Reheat pump/internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.
Units with Secondary Pump or Condenser Hot Water Reheat