I n s t a l l a t i o n , O p e r a t i o n , M a i n t e n a n c e
25
JE-Series
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
I s s u e D a t e :
M a y 1 0 , 2 0 2 1
Electrical Data
Units with Variable Pump High Head
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Pump FLA
Fan
Motor FLA
Total
Unit FLA
Min
Circ Amp
Max Fuse/
HACR
RLA
LRA
Qty
026
G
208/230/60/1
197/252
11.7
58.3
1
1.44
3.9
17.0
20.0
30
E
265/60/1
239/292
9.1
54.0
1
1.25
3.2
13.6
15.8
25
H
208/230/60/3
197/252
6.5
55.4
1
1.44
3.9
11.8
13.5
20
*F
*460/60/3
414/506
3.5
28.0
1
1.25
3.2
8.0
8.8
15
038
G
208/230/60/1
197/252
15.3
83.0
1
1.44
3.9
20.6
24.5
40
E
265/60/1
239/292
13.0
72.0
1
1.25
3.2
17.5
20.7
30
H
208/230/60/3
197/252
11.6
73.0
1
1.44
3.9
16.9
19.8
30
*F
*460/60/3
414/506
5.7
38.0
1
1.25
3.2
10.2
11.6
15
049
G
208/230/60/1
197/252
21.2
104.0
1
1.44
6.9
29.5
34.8
50
E
265/60/1
239/292
16.0
109.7
1
1.25
6.0
23.3
27.3
40
H
208/230/60/3
197/252
14.0
83.1
1
1.44
6.9
22.3
25.8
40
*F
*460/60/3
414/506
6.4
41.0
1
1.25
6.0
13.7
15.3
20
064
G
208/230/60/1
197/252
27.1
152.9
1
1.44
6.9
35.4
42.2
60
E
265/60/1
239/292
22.4
130.0
1
1.25
6.0
29.7
35.3
50
H
208/230/60/3
197/252
16.5
110.0
1
1.44
6.9
24.8
29.0
45
*F
*460/60/3
414/506
7.2
52.0
1
1.25
6.0
14.5
16.3
20
072
G
208/230/60/1
197/252
29.7
179.2
1
1.44
6.9
38.0
45.5
70
H
208/230/60/3
197/252
17.6
136.0
1
1.44
6.9
25.9
30.3
45
*F
*460/60/3
414/506
8.5
66.1
1
1.25
6.0
15.8
17.9
25
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/internal pumps require a four wire power supply with neutral. ECM motors/internal
pumps are rated 265 vac and are wired between one hot leg and neutral.
Units with Variable Pump Standard Head
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Pump FLA
Fan
Motor FLA
Total
Unit FLA
Min
Circ Amp
Max Fuse/
HACR
RLA
LRA
Qty
026
G
208/230/60/1
197/252
11.7
58.3
1
0.7
3.9
16.3
19.2
30
E
265/60/1
239/292
9.1
54.0
1
0.6
3.2
12.9
15.2
20
H
208/230/60/3
197/252
6.5
55.4
1
0.7
3.9
11.1
12.7
15
*F
*460/60/3
414/506
3.5
28.0
1
0.6
3.2
7.3
8.2
15
038
G
208/230/60/1
197/252
15.3
83.0
1
0.7
3.9
19.9
23.7
35
E
265/60/1
239/292
13.0
72.0
1
0.6
3.2
16.8
20.1
30
H
208/230/60/3
197/252
11.6
73.0
1
0.7
3.9
16.2
19.1
30
*F
*460/60/3
414/506
5.7
38.0
1
0.6
3.2
9.5
10.9
15
049
G
208/230/60/1
197/252
21.2
104.0
1
0.7
6.9
28.8
34.1
50
E
265/60/1
239/292
16.0
109.7
1
0.6
6.0
22.6
26.6
40
H
208/230/60/3
197/252
14.0
83.1
1
0.7
6.9
21.6
25.1
35
*F
*460/60/3
414/506
6.4
41.0
1
0.6
6.0
13.0
14.6
20
064
G
208/230/60/1
197/252
27.1
152.9
1
0.7
6.9
34.7
41.5
60
E
265/60/1
239/292
22.4
130.0
1
0.6
6.0
29.0
34.6
50
H
208/230/60/3
197/252
16.5
110.0
1
0.7
6.9
24.1
28.2
40
*F
*460/60/3
414/506
7.2
52.0
1
0.6
6.0
13.8
15.6
20
072
G
208/230/60/1
197/252
29.7
179.2
1
0.7
6.9
37.3
44.7
70
H
208/230/60/3
197/252
17.6
136.0
1
0.7
6.9
25.2
29.6
45
*F
*460/60/3
414/506
8.5
66.1
1
0.6
6.0
15.1
17.2
25
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/internal pumps require a four wire power supply with neutral. ECM motors/internal
pumps are rated 265 vac and are wired between one hot leg and neutral.