Johnson Controls IOM2710 Installation Instructions Manual Download Page 4

IOM2710 and IOM3710 Input/Output Modules Installation Instructions

4

3.

If the IOM is connected to the SA Bus of an NCE or 
FEC, wire the SA Bus in a daisy chain (Figure 6).

Note:

The SA/FC Bus Port (RJ-12 6-position 

modular connector) provides 15 VDC on one of its 
pins, which is used to power the MS-BTCVT.

Note:

If the IOM controller is at one end of the SA 

Bus daisy chain, set the End-of-Line (EOL) switch 
to ON.

4.

Connect power to the IOM controller.

5.

Download and commission the IOM controller. See 
the 

Commissioning

 section. 

SA/FC Bus Port

The SA/FC Bus port on the front of the IOM is an 
RJ-12, 6-position modular jack that provides a 
connection for the Wireless Commissioning Converter.  
See Table 1 for more information. The SA/FC Bus Port 
pin assignment is shown in (Figure 7).   

 

   

Figure 5: FC Bus Terminal Block Wiring

 Stranded 3-Wire Twisted Shielded Cable

Isolated Shield

Connection

Terminal

+

_

CO

M

SH

L

D

To Next

Device on

the FC Bus

Segment

FC Bus

Terminal

Block Plugs

F

IG

: f

c_

bus

_t

er

m

s

+

_

CO

M

SH

L

D

Terminating Device

on FC Bus Segment

To Next

Device on

the FC Bus

Segment

Daisy Chained Device 

on FC Bus Segment

 Stranded, 4-Wire (2 Twisted Pair) Shielded Cable

(One twisted pair is the   and  leads. 

The second pair is COM and SA PWR.) 

+

 

-

Cable Shield

Connection

To Next

Device on

the SA Bus

F

IG

:s

a_b

us

_

te

rm

s

SA Bus

Terminal

Block Plugs

Terminating Device

on SA Bus

Daisy Chained Device 

on SA Bus

To Next

Device on

the SA Bus

+

CO

M

SA

 PW

R

+

CO

M

SA

 PW

R

Figure 6: SA Bus Terminal Block Wiring

Figure 7: Pin Number Assignments for 

Sensor, SA Bus, and FC Bus Ports on 

FEC, IOM, and VMA16

Power

 (15 VDC)

SA or FC Bus +

SA or FC Bus 

-

Bus and Power Common 

Power 

(15 VDC)

Sensor, SA Bus, or FC Bus Port

(RJ-12 Modular Jack)

Bus and Power Common 

F

IG

:R

J_pi
n

o

ut

2

3

4

5

6

1

Summary of Contents for IOM2710

Page 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Page 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Page 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Page 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Page 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Page 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Page 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Page 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Page 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Page 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...