Johnson Controls IOM2710 Installation Instructions Manual Download Page 3

IOM2710 and IOM3710 Input/Output Modules Installation Instructions

3

3.

Drill holes in the wall at the locations marked in 
Step 2 and insert wall anchors (if necessary).

4.

Position the IOM controller and insert the screws 
through the holes in the mounting clips, and 
carefully tighten all the screws.

DIN Rail Mount Applications

To mount the IOM controller on a DIN rail:

1.

Securely mount the section of DIN rail horizontally 
and centered in the required space.

2.

Carefully pull down (outward) the bottom mounting 
clips until they lock in place (Figure 4).

Note:

The top mounting clip is not used on DIN 

rail applications. You may remove the clip.

3.

Hang the IOM controller on the DIN rails using the 
DIN rail hooks on the back of the IOM controller.

4.

Secure the IOM controller on the DIN rail by 
pressing the bottom mounting clips up until they 
snap into place.

To remove the IOM controller from the DIN rail, snap 
the bottom DIN clips to the outboard position and 
carefully lift the IOM controller off the DIN rail.

Wiring   

  

 

Refer to the 

MS/TP Communications Bus Technical 

Bulletin (LIT-12011034) 

for more information on 

Master-Slave/Token-Passing (MS/TP) devices.

To wire the IOM controller:

1.

Terminate wiring per engineering drawings.

2.

If the IOM is connected to the FC Bus of a Network 
Automation Engine (NAE) or Network Control 
Engine (NCE), wire the FC Bus in a daisy chain.

IMPORTANT:

 Do not overtighten the mounting 

screws. Overtightening the screws may damage the 
mounting clips or IOM housing.

48

1-7/8

(

)

90

3-1/2

(

)

90

3-1/2

(

)

143

5-5/8

(

)

127

5

( )

DIN Rail
Channel

DIN Rail

Hooks

95

3-3/4

(

)

F

IG

IO

M

2

7

1

0

_

3

7

1

0

_

m

n

t_

d

im

Mounting Clips

(in Extended Positions)

48

1-7/8

(

)

48

1-7/8

(

)

Figure 2: IOM2710 and 3710 Controller Mounting 

Features, mm (in.)

IMPORTANT:

Do not connect 24 VAC supply 

power to the IOM controller before finishing wiring 
and checking all wiring connections. Short circuits or 
improperly connected wires may result in permanent 
damage to the equipment.

IMPORTANT:

Use copper conductors only. Make 

all wiring in accordance with local, national, and 
regional regulations. The IOM controller is a 
low-voltage (<30 VAC) device. Do not exceed the 
IOM controller electrical ratings.

IMPORTANT:

Prevent any static electric discharge 

to the IOM controller. Static electric discharge can 
damage the IOM controller and void any warranties.

Figure 4: Required Orientation for DIN Rail 

Mount Applications

FAULT

POWER

ADDRESS

ON

+1

5

V

+5

V

IN

 1

IC

O

M

 1

IN

 2

IC

O

M

 2

+

15V

+5

V

IN

 3

IC

O

M

 3

IN

 4

IC

O

M

 4

UNIVERSAL

CO

M

+

+

CO

M

SA

PW

R

CO

M

HO

T

OU

T

 7

OC

OM

 7

OU

T

 8

OC

OM

 8

OU

T

 5

OC

OM

 5

OU

T

 6

OC

OM

 6

OU

T

 4 N

O

OC

OM

 4

OU

T

 4 N

C

OU

T

 3 N

O

OC

OM

 3

OU

T

 3 N

C

OU

T

 2 N

O

OC

OM

 2

OU

T

 2 N

C

OU

T

 1 N

O

OC

OM

 1

OU

T

 1 N

C

ADDRESS Ø = ALL OFF

EOL

O
N

FI

G

:I

O

M

2

73

7

10_

D

IN

Summary of Contents for IOM2710

Page 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Page 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Page 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Page 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Page 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Page 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Page 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Page 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Page 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Page 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...

Reviews: