IOM2710 and IOM3710 Input/Output Modules Installation Instructions

5

Table 1:  IOM2710 and IOM3710 Controller Wiring List (Part 1 of 2)

Terminal 
Block

1

Terminal 
Labels

Function and Electrical Ratings/Requirements

Wiring Requirements 
(See Table 2 fo
r A, B, or C.)

Universal IN

+5 V

Sources 5 VDC power for active devices
60 mA total current

Same as IN

+15 V

Sources 15 VDC power for active devices
35 mA total current

Same as IN

IN 

n

Analog Input, Voltage Mode
Accepts a 0-10 VDC input signal.
10 VDC Maximum Input Voltage
Internal 75k ohm Pulldown

A

Analog Input, Current Mode
Accepts a 4-20 mA input signal.

Note:

For current sensing applications, the IOM2710 

and IOM3710 Controllers do not provide a jumper to 
close the current loop when the controller is powered off. 
This option is available on IOM4710 Controllers only.

B

Analog Input, Resistive Mode
Accepts 0-600k ohm input signal.
Internal 12 V, 15k ohm Pullup

A

Binary Input, Dry Contact Maintained Mode
1 s minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup

A

Binary Input, Dry Contact Pulse Counter Mode
1 s minimum pulse width (0.5 Hz at 50% duty cycle)
Internal 12 V, 15k ohm Pullup

A

ICOM 

n

The input signal common for Universal IN terminals; 
isolated from all other terminal commons.

Same as IN

Universal 
OUT

OUT 

n

Analog Output, Voltage Mode
Sources 0-10 VDC output voltage
1k ohm minimum load
10 VDC maximum output voltage
10 mA maximum output current

A

Binary Output Mode
24 V AC/DC FET
Connects OUT to OCOM when activated.
30 V AC/DC maximum output voltage
0.5 A maximum output current
40 mA minimum load current (hold current)

B

Analog Output, Current Mode
Sources 4-20 mA output current
External 300 ohm maximum load required

B

OCOM 

n

The output signal common; isolated from all other 
terminal commons, including UO terminal commons.

Same as OUT

Summary of Contents for IOM2710

Page 1: ...In Metasys system smoke control applications use only the IOM2710 and IOM3720 models that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 8 for UUKL 864 Listed IO...

Page 2: ...FAULT POWER ADDRESS ON 15V 5V IN 1 ICOM 1 IN 2 ICOM 2 15V 5V IN 3 ICOM 3 IN 4 ICOM 4 UNIVERSAL COM COM SA PWR COM HOT OUT 7 OCOM 7 OUT 8 OCOM 8 OUT 5 OCOM 5 OUT 6 OCOM 6 OUT 4 NO OCOM 4 OUT 4 NC OUT 3...

Page 3: ...s connected to the FC Bus of a Network Automation Engine NAE or Network Control Engine NCE wire the FC Bus in a daisy chain IMPORTANT Do not overtighten the mounting screws Overtightening the screws m...

Page 4: ...Figure 7 Figure 5 FC Bus Terminal Block Wiring Stranded 3 Wire Twisted Shielded Cable Isolated Shield Connection Terminal _ COM SHLD To Next Device on the FC Bus Segment FC Bus Terminal Block Plugs FI...

Page 5: ...only B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup A Binary Input Dry Contact Maintained Mode 1 s minimum pulse width 0 5 Hz at 50 duty cycle Internal 12...

Page 6: ...M Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm2 18 to 24 AWG 22 AWG Recommended FC Bus1 COM Provides FC Bus communication network Daisy chained 1 524...

Page 7: ...lications Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 A...

Page 8: ...tches Set to 21 FIG fec_dip_swtch 128 64 32 16 8 4 2 1 ON Note Switch 128 is used to enable or disable an FEC for wireless operation Figure 10 EOL Switch Positions FIG EOL_Swtch EOL ON Position EOL Of...

Page 9: ...VA maximum plus all BO and Configurable Output loads Ambient Conditions Operating 0 to 50 C 32 to 122 F 10 to 90 RH noncondensing Storage 40 to 70 C 40 to 158 F 10 to 90 RH noncondensing Terminations...

Page 10: ...EC in accordance with EN 61000 6 3 2001 Generic Emission Standard for Residential and Light Industry and EN 61000 6 2 2001 Generic Immunity Standard for Heavy Industrial Environment and the Low Voltag...