14
Johnson Controls, Inc. SLC Wiring Manual —
P/N 51870:G 04/23/2009
Introduction
Devices
1951J
Addressable, intelligent smoke detector that incorporates an ionization sensing chamber.
Designed to provide open area protection. FlashScan- and CLIP-mode capable. (An earlier model
named
1351J
was also FlashScan capable. Earlier models named
1251J
and
1551J
were CLIP
mode only.)
2951J
Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber.
Listed for use in ducts. Designed to provide open area protection. The
2951TJ
adds thermal sensors
that will alarm at a fixed temperature of 135° F (57.2°C). Both models support FlashScan or CLIP
mode. (Earlier versions named
2351J
and
2351TJ
also supported FlashScan or CLIP mode, but
were not listed for use in ducts. Earlier models named
2551J, 2251J
and
2251THJ
were CLIP mode
only.)
5951J
Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot spacing capability. A fixed temperature sensor with 135°F (57.2°C) fixed
temperature alarm. The
5951RJ
incorporates a thermal rate of rise of 15°F (8.3°C). The
5951HJ
is
a high temperature sensor with 190°F (87.8°C) fixed temperature alarm. Both models support
FlashScan or CLIP mode. (Earlier versions named
5351J
and
5351RJ
also supported FlashScan or
CLIP mode. Earlier models named
5551J
and
5551JR
were CLIP mode only.)
DH300P
Photoelectric Duct Detector. The
DH300RP
includes an alarm relay. Both models
support FlashScan or CLIP mode.
DH300PL
Low-flow Photoelectric Duct Detector, with extended speed range of 100–4000 FPM
(0.5 m/s to 20.3 m/s).
DH300RPL
adds a relay. Both models support FlashScan or CLIP mode.
FTX-P2J (HARSH™)
A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. Supports FlashScan or
CLIP mode. (An earlier model named
FTX-P1J
was CLIP mode only.)
7351J VIEW®
An advanced intelligent photoelectric detector that uses a laser diode, special
optics, and signal processing to obtain extremely high sensitivity. Supports FlashScan and CLIP
mode; compatible with IFC-300/IFC-400, IFC-320, IFC2-640, IFC-640, and IFC-3030/IFC2-3030
only.
LPX-751L
is compatible with IFC-200 and IFC-1010/IFC-2020; CLIP mode only. (An
earlier version named
7251J
was CLIP mode only and compatible with IFC-300/IFC-400.)
1.6.8 Addressable Manual Pull Stations
The
JBG-12LX
is a dual-action pull station that, when activated, provides an addressable
identification and its location to the control panel. An addressable monitor module is mounted
inside the pull station to facilitate servicing and replacement. Supports FlashScan or CLIP mode.
An earlier model named BGX-101L was CLIP mode only.
1.6.9 RFX Wireless Interface
The RFX Wireless Interface allows communication between an intelligent addressable fire alarm
control panel and up to 80 wireless smoke detectors. The RFX Interface, which includes a wireless
receiver, monitors the status of each wireless detector and forwards this information to the control
panel through the SLC. This system uses the
SDRF-751
Wireless Photo-Thermal Smoke Detector,
which is battery-powered and designed to operate with the RFX Wireless Interface. FlashScan
capable. Not suitable for Canadian applications. The RFX and associated devices were
discontinued as of December 31, 2005.
1.6.10 ACPS-610/E Addressable Charger/Power Supply
The ACPS-610/E is an addressable power supply and battery charger with 24 VDC outputs. It
operates in FlashScan or CLIP mode and has built-in strobe synchronization. Its four outputs may
be independently configured to drive Notification Appliance Circuits (NACs) or to provide
auxiliary power.