background image

54

Johnson Controls, Inc. SLC Wiring Manual —

  P/N 51870:G  04/23/2009

Power Considerations

Supervising 24 VDC Power

A.2  Supervising 24 VDC Power

There are options for supervising 24 VDC power, as discussed below.

Using FlashScan Type Codes with Built-In Power Supervision (IFC-3030 only)

Power Supervision Relay

Using the M300CJ module without relay

A.2.1  Using Type Codes with Built-In Power Supervision on 

IFC-3030 

Certain FlashScan type codes have external power supervision built into the software. For details, 
refer to “Devices Requiring External Power Supervision” in the appropriate installation manual

.

A.2.2  Power Supervision Relay

Power used to supply 24 VDC detectors, notification appliances (using the M300CJ) and two wire 
detectors (using the M302MJ) can be supervised with a power supervision relay. This relay, 
energized by the 24 VDC power itself, is installed at the end of each respective power run and 
wired in line with the supervised circuit of any intelligent module.

When power is removed from the relay, the normally closed contacts open the supervised circuit, 
generating a trouble condition. Therefore, the relay needs to be installed at the end of the 
supervised circuit, so as to not disrupt the operating capability of all the devices on that circuit. The 
relay can be installed in line with any leg (+ or –) of the supervised NAC or IDC circuit, either a 
two or a four-wire style.

See Figure A.1 and Figure A.2. Refer to the 

Device Compatibility Document

 for compatible 

notification appliances and relays.    

Figure A.1  Supervised 24 VDC Circuit 

SL

C-

ps

rt

p

H

.c

dr

24 VDC Power from 

Control Panel or 

Power Supply

Power Supervision 

Relay

(EOLR-1)

Supervised NAC or IDC

ELR 

(Use 47K with M300CJ 

or 3.9K with M302MJ)

Last device on the SLC loop 

(M300CJ or M302MJ) 

Summary of Contents for IFC-1010

Page 1: ...G P N 51870 G ECN 08 704 Document 51870 04 23 2009 Intelligent Control Panel SLC Wiring Manual ...

Page 2: ...of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter mined rate or reaches a pr...

Page 3: ...s Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage ...

Page 4: ...appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for p...

Page 5: ...rmance 15 1 9 LED Operation 16 Section 2 Wiring Requirements 17 2 1 Recommended SLC Wiring 17 2 2 Two Wire SLC Style 4 Class B 18 2 2 1 Measuring Loop Resistance 18 2 2 2 Measuring Total Wire Length 19 2 3 Four Wire SLC Style 6 7 Class A 19 2 3 1 Measuring Loop Resistance 19 2 3 2 Measuring Total Wire Length 20 2 4 Control Panel Terminal Blocks 20 2 4 1 IFC2 3030 and IFC 3030 with LCM 320 LEM 320 ...

Page 6: ...Wiring a Style Y NAC Two Wire with Addressable Control Modules 43 7 4 Wiring a Style Z NAC Four Wire with Addressable Control Modules 44 7 5 Connecting a Releasing Device to the Addressable Control Module 45 Section 8 Relay Module 47 8 1 Description 47 8 2 Wiring the Addressable Relay Module Form C Relay 47 Section 9 Intelligent Detector Bases 48 9 1 Description 48 9 2 Wiring a Detector Base 48 9 ...

Page 7: ...Table of Contents Johnson Controls Inc SLC Wiring Manual P N 51870 G 04 23 2009 7 C 2 M300CJ and M302MJ 64 C 3 M300MJ 65 Appendix D Canadian Versions of SLC Devices 66 ...

Page 8: ... now available in this new format and have replaced the old format illustrations in this manual While the old format is no longer manufactured for these models Appendix C has been provided for those who need that wiring information it contains terminal conversion charts between the old and new formats In this appendix the modules are referred to as h type the new format which has horizontal rotary...

Page 9: ...s Non addressable Document Number Device Compatibility Document Device Compatibility Technical Bulletin 51922 LIT 445180 Fire Alarm Control Panel FACP and Main Power Supply Installation Document Number IFC 200 Instruction Manual Technical Manual 444 IFC 300 400 Installation Operations and Programming Manual Technical Manual 443 IFC 640 Installation Operations and Programming Manuals 51864 51865 51...

Page 10: ...6 B210LPJ Flanged Base Installation Document I56 727 2351TMJ Acclimate Multi Sensor Detector Installation Document I56 1860 2951TMJ See document for 2951J 2951TJ and 2951TMJ M300CJ Control Module Installation Document I56 1210 M300CJ REL Control Module Installation Document I56 XXXX M300DJ Dual Monitor Module Installation Document I56 0016 M300MJ Monitor Module Installation Document I56 1211 M300M...

Page 11: ...ps on IFC 320 can run in FlashScan mode or CLIP mode IFC 200 IFC 300 IFC 400 IFC 1010 and IFC 2020 run in CLIP mode only Many FlashScan devices can be programmed to run in either CLIP or FlashScan mode Use one of the following three options with SLC loops 1 Program all modules and detectors on an SLC as FlashScan 2 Program all modules and detectors on an SLC as CLIP 3 Program all detectors as CLIP...

Page 12: ...nes of conventional two wire detectors FlashScan or CLIP mode XP10 M Supervises ten Class B addressable Initiating Device Circuits IDC which monitor normally open contact initiating devices FlashScan or CLIP mode This module is capable of participating in degraded mode where supported by the FACP 1 6 2 Control Modules Through these addressable modules the control panel can selectively activate Not...

Page 13: ...r to standard bases but have sound or relay capabilities Standard Base Models B501J 4 inch standard small diameter base commonly used in European installations and B210LPJ 6 inch standard large diameter base commonly used in US installations HARSH Base Model B501B FTXJ Isolator Base Model B224BI isolator base Sounder Base Models B501BH standard sounder base and B501BHT base with temporal sounder R...

Page 14: ...ection in hostile environments where traditional smoke detectors are not practical Supports FlashScan or CLIP mode An earlier model named FTX P1J was CLIP mode only 7351J VIEW An advanced intelligent photoelectric detector that uses a laser diode special optics and signal processing to obtain extremely high sensitivity Supports FlashScan and CLIP mode compatible with IFC 300 IFC 400 IFC 320 IFC2 6...

Page 15: ...figuration of the circuit and the components on the circuit see Table 1 2 SLC operation meeting Style 7 requirements isolates each addressable device on the SLC from faults that may occur on the SLC Wiring style requirements are determined by national and local codes Consult with the Authority Having Jurisdiction before wiring the SLC The table below derived from NFPA 72 2002 lists the trouble con...

Page 16: ...Blinks GREEN Blinks RED RED continuous 2 sec GREEN then OFF RED continuous N A N A N A N A N A N A IFC 300 IFC 400 Monitor Module Control Module Detector Blinks RED Blinks GREEN Blinks RED RED continuous GREEN continous RED continuous N A N A N A N A N A N A IFC 200 Monitor Module Control Module Detector Blinks RED Blinks GREEN Blinks RED RED continuous OFF RED continuous N A N A N A N A N A N A I...

Page 17: ...of Style 6 7 loops 50 ohms per branch maximum for Style 4 loop 12 500 ft 3 810 m 9 500 ft 2 895 6 m 6 000 ft 1 828 8 m 3 700 ft 1 127 76 m 12 AWG 3 31 mm 14 AWG 2 08 mm 16 AWG 1 31 mm 18 AWG 0 82 mm Untwisted unshielded wire in conduit or outside of conduit 1 000 ft 304 8 m 12 to 18 AWG 3 31 mm to 0 82 mm Note Twisted shielded pair is not recommended for use with this panel Note Maximum total capa...

Page 18: ... for Style 4 loops 10 000 ft 3 048 m 8 000 ft 2 438 4 m 4 875 ft 1 485 9 m 3 225 ft 982 98 m 12 AWG 3 31 mm 14 AWG 2 08 mm 16 AWG 1 31 mm 18 AWG 0 82 mm Untwisted unshielded wire in conduit or outside of conduit 1 000 ft 304 8 m 12 to 18 AWG 3 31 mm to 0 82 mm Note Twisted unshielded pair wire is not recommended for use with this panel Note Maximum total capacitance of all SLC wiring both between ...

Page 19: ...ould be summed twice Figure 2 2 Measuring the Total Wire Length of a Two wire SLC 2 3 Four Wire SLC Style 6 7 Class A 2 3 1 Measuring Loop Resistance The total DC resistance of the SLC pair exceed 50 ohms 50 ohms for IFC 320 IFC2 640 IFC 640 LCM 320 LEM 320 JLIB 200A and JLIB 400 40 ohms for IFC 200 IFC 300 400 and JLIB 200 Measure DC resistance as detailed and shown below 1 Disconnect the SLC cha...

Page 20: ...trol Panel Terminal Blocks 2 4 1 IFC2 3030 and IFC 3030 with LCM 320 LEM 320 The IFC 3030 IFC2 3030 supports up to five pairs of loop control and expander modules providing from one to ten SLC loops Loops can be either CLIP mode or FlashScan mode SLC loops connect to TB1 on the LCM 320 or LEM 320 Figure 2 5 IFC2 3030 IFC 3030 SLC Loop Connections and Wiring SLC meas5 cdr SLC Out SLC Return Short P...

Page 21: ...th Loop Expander Modules The IFC 640 provides one SLC loop and supports a second using optional expander module LEM 320 Loops can be either CLIP mode or FlashScan mode SLC loop 1 connects to TB16 on the control panel SLC loop 2 connects to TB1 on the LEM 320 Figure 2 7 SLC Loop Connections and Wiring 2 4 4 IFC 200 IFC 200 supports one SLC loop the loop is CLIP mode only The SLC loop connects to TB...

Page 22: ...e CLIP mode only SLC loops connect to TB1 and TB2 on JLIB 400 and TB1 on JLIB 200A Figure 2 10 SLC Connections for JLIB 200A JLIB 400 SLC Loop 1 Connections on s main circuit board SLC Loop Connections on s main circuit board slc 300 wmf slc 400 wmf SLC Loop 1 Connections on FACP s main circuit board slc 400 wmf slc lib 200a wmf slc lib 400 wmf Pin 1 SLC Loop Port A Pin 3 SLC Loop Port A Pin 5 SLC...

Page 23: ...B 200A or JLIB 400 If twisted shielded wire is used in one of these installations use a floating shield to terminate the wire as shown in Section 3 5 Floating Shield on page 25 Use of good wiring practice consistent with local electrical codes is expected 3 2 No Conduit For use with IFC 200 IFC 300 400 and JLIB 200 only Scrape the paint on the cabinet to bare metal to provide a good electrical con...

Page 24: ...junction box by using a proper connector Scrape the paint on the cabinet to bare metal to provide a good electrical connection Connect the metal conduit between the junction box and the cabinet by using the proper connectors Feed the twisted pair wire into the junction box through the conduit into the cabinet box Within the junction box connect the appropriate wires together using wire nuts Connec...

Page 25: ...ire is used in these installations use a floating shield to terminate the wire The following precautions must be met If the SLC is more than 3000 ft 914 4 m divide the shield into floating segments of less than 1000 ft 304 8 m To divide the shield wire into floating segments cut shield even with jacket and tape as shown Figure 3 4 Floating the Shield NOTE Using shielded wire in applications where ...

Page 26: ...of circuits that do not require isolation devices NFPA 72 Style 4 NFPA 72 Style 6 4 2 NFPA Style 4 SLC NFPA Style 4 requirements can be met by using the diagram below T tapping of the SLC wiring is allowed for Style 4 configuration Figure 4 1 Basic NFPA Style 4 SLC SLC style4 cdr Two wire Addressable Detector Addressable Module T tapped Circuits Control Panel SLC B B ...

Page 27: ...lators 4 3 NFPA Style 6 SLC NFPA Style 6 requirements can be met by using the diagram below Figure 4 2 Basic NFPA Style 6 SLC NOTE T tapping of the SLC wiring is NOT allowed for Style 6 configuration Control Panel SLC Two wire Addressable Detector Addressable Module SLC style6 cdr SLC Return SLC Out B B A A ...

Page 28: ...essable devices on the remaining branches labeled Continuation of the SLC in the figure belowFigure 5 1 During a fault condition the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch Once the fault is removed the module automatically reapplies power to the SLC branch or segment 5 2 1 Wiring an Isolator Module Figure 5 1 shows a S...

Page 29: ... detectors 5 3 1 How an Isolator Base Works If a short circuit fault occurs at point X devices A B C detector 2 will cease to function and display a trouble warning at the control panel Devices D E F detectors 1 3 4 and 5 will remain normal as they are served by SLC Return If a short circuit fault occurs at point Y all devices will continue to function If a short circuit fault occurs at point Z on...

Page 30: ...4 operation using isolator modules to protect each branch of the SLC Refer to Figure 5 1 on page 28 for M500XJ wiring and to Section 5 1 Overview for limitations Two wire Addressable Detector Addressable Pull Station SLC style4iso cdr Control Panel SLC B B Isolated Branch Isolator Module Isolator Module Isolator Module Isolated Branch Isolated Branch Figure 5 3 NFPA Style 4 SLC Using M500XJ Module...

Page 31: ...ithin the Style 6 configuration Isolator modules shall be within 20 ft 6 1 m of device and the wire must be enclosed in metal conduit SLC Out SLC Return SLC style6iso cdr Control Panel Two wire Addressable Detector Addressable Pull Station Section B Section C Section A IFC 200 IFC 1010 IFC 2020 The first isolator module on SLC Out and SLC Return must be contained within the same enclosure as the F...

Page 32: ...isolator module as shown in Figure 9 3 There must be a close nipple connection between a device and the isolator bases or modules that protect it Figure 5 5 NFPA Style 7 SLC NOTE See Figure 9 3 Wiring an Isolator Base on page 50 SLC style7iso cdr SLC Out SLC Return Addressable Detector Two wire Isolator Detector Base Addressable Pull Station Control Panel IFC 200 IFC 2020 IFC 1010 The first isolat...

Page 33: ...nual 6 1 1 Addressable Monitor Module M300MJ is an addressable modules that monitors either a Style B Class B or Style D Class A IDC of dry contact input devices This module is capable of participating in degraded mode where supported by the FACP Figure 6 1 M300MJ Monitor Module 6 1 2 Zone Interface Module M302MJ is similar to the M300MJ except it is used to monitor compatible two wire 24 volt con...

Page 34: ...4 20 is intended for use in intelligent two wire systems allowing Control Panels to interface and monitor two wire or three wire sensors with a 4 20mA signal output Figure 6 5 M300MJ 4 20 4 20mA Monitor Module SLCDualMod simplified wmf Rotary Switches SLC SLC 9 H 8 H 7L 6L Address 1 Base Address Areas used to record the device address and SLC number 0 10 11 12 13 14 15 ADDRESS LOOP 1 2 3 4 TENS ON...

Page 35: ... switches on the module to the desired address The unit shown in Figure 6 6 is set at address 35 When finished mark the address on the module face in the place provided Figure 6 6 Setting SLC Address on Module Type H Rotary Switches Breakaway Tab Modules come with a raised breakaway tab on the TENS rotary switch This tab must be removed when the module is on an FACP that uses more than 99 addresse...

Page 36: ...evice Circuit IDC is supervised and current limited to 210 microamps 24 VDC nominal 2 The IDC provides the following services do not mix Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervisory service with normally open contact devices Security service 3 Refer to the Device Compatibility Document for compatible smoke detectors 4 See ...

Page 37: ...evice Circuit IDC is supervised and current limited to 210 microamps 24 VDC nominal 2 The IDC provides the following services do not mix Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervisory service with normally open contact devices Security service 3 Refer to the Device Compatibility Document for compatible smoke detectors 4 See ...

Page 38: ...sing of modules on the system Each IDC H L is power limited to 230 microamps 24 VDC Figure 6 9 shows typical wiring for a supervised and power limited NFPA Style B Class B Initiating Device Circuit using the M300DJ dual monitor Module installation notes 1 The Initiating Device Circuit IDC is supervised and current limited to 210 microamps 24 VDC nominal 2 The IDC provides the following services do...

Page 39: ...evice Circuit IDC is supervised and current limited to 210 microamps 24 VDC nominal 2 The IDC provides the following services do not mix Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervisory service with normally open contact devices Security service 3 Refer to the Device Compatibility Document for compatible smoke detectors Figure...

Page 40: ...ing Device Circuit IDC is supervised and current limited to 210 microamps 24 VDC nominal 2 The IDC provides the following services do not mix Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervisory service with normally open contact devices Security service 3 Refer to the Device Compatibility Document for compatible smoke detectors F...

Page 41: ... configured for NFPA Class B or Class A wiring When using the M300CJ REL for Class B applications remove jumper J1 refer to Figure 7 4 on the back Refer to the Device Compatibility Document for a list of compatible UL Listed Fire Alarm Releasing Solenoids For more information on the module specifications refer to the Installation Instructions provided with these devices Setting an SLC Address Each...

Page 42: ...it see the Voice Alarm System Manual FireVoice 25 50 Manual or DVC Manual as appropriate for your equipment and when supervising 24VDC NAC power using the no relay alternative wiring see Appendix A 2 3 Using the Addressable Control Module Without Relay J1 Rear View To remove J1 from the 1 Insert a small prying tool such as a screwdriver or probe behind J1 2 Using the tip of the prying tool slide J...

Page 43: ...run IFC 3030 only If using one of the IFC 3030 s FlashScan type IDs that provide built in power supervision no relay is required 4 Do not Tap or branch a Style Y circuit 5 Terminate the circuit across the last device using a UL listed End of Line Resistor 47K 1 2 watt SSD P N A2143 00 ELR 47K in Canada 6 Do not loop wiring under the screw terminals of any notification appliance To maintain supervi...

Page 44: ...power supervision relay is required only on the last module of the power run IFC 3030 only If using one of the IFC 3030 s FlashScan type IDs that provide built in power supervision no relay is required 4 Do not T Tap or branch a Style Z circuit 5 Do not loop wiring under the screw terminals of any notification appliance To maintain supervision break the wire run at each device 6 Refer to the Devic...

Page 45: ... VDC power 2 Do not T tap or branch a Style Y or Style Z circuit 3 Only one 1 24V solenoid or two 2 12V solenoids in series can be connected to the M300CJ REL SLC SLC NON RESETABLE 24 VDC POWER SUPPLY ISOLATED REGULATED POWER LIMITED PER NFPA 70 LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP Compatible UL listed 24 VDC releasing device One 1 device maximum Module polarities are shown in alarm cond...

Page 46: ...ovide supervision of connections 5 All applications using the M300CJ REL are power limited a Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT b Circuits are supervised against opens and shorts 6 Refer to your FACP s Programming Manual for instructions on setting the Soak Timer The M300CJ REL module must be programmed with the correct releasing type code listed in your FACP s ...

Page 47: ...e g Using a smaller relay to trip another relay For more information on the module specifications refer to the Installation Instructions provided with this device For information on transponders refer to the specific transponder manual Setting an SLC Address Each relay module is factory preset with an address of 00 To set an SLC address refer to Section 6 2 Setting an SLC Address for a Module on p...

Page 48: ...Detector Address Each intelligent detector head is factory preset with an address of 00 To set an SLC address refer to Setting an SLC Address for a Module on page 35 9 2 Wiring a Detector Base Figure 9 1 shows typical wiring of the B210LPJ or B501J detector base connected to an SLC An optional RA400Z Remote LED Annunciator is shown connected to the base Figure 9 1 Wiring of the B501J Detector Base...

Page 49: ...a HARSH detector connected to an SLC An optional RA400Z Remote LED Annunciator is shown connected to the base Figure 9 2 Wiring of the B501B FTXJ Detector Base RA400Z Remote LED Annunciator Optional SLC To next device on SLC Power to next device B710HD wmf For connection of cable shield To compatible UL Listed Power Supply NOTE Use a spade lug to wire the Remote LED Annunciator to Terminal 2 ...

Page 50: ...s 1 and 2 In Style 7 applications the loss of a single detector during a short circuit is not acceptable and an isolator module must be installed as shown in the figure below Figure 9 3 Wiring an Isolator Base 9 4 Wiring a Relay Base Figure 9 4 shows typical wiring of the B224RB plug in relay detector base connected to an SLC Figure 9 4 Wiring of the B224RB Plug in Relay Detector Base SLC In SLC O...

Page 51: ...bases Figure 9 5 Wiring of the B501BH B501BHT Sounder Bases B501BHWiring wmf Class A Optional Wiring Optional Sounder Interconnect SLC B SLC B Power Power UL listed Compatible FACP Class A Optional Wiring External 24V Supply Intelligent Monitor Module UL listed EOL Relay 24V UL listed EOL Resistor 47K Grouping of up to 6 model B501BHT temporal tone sounder bases OUT 4 5 IN 3 External supply 2 1 4 ...

Page 52: ...efer to the Installation Instructions document provided with the devices Setting an SLC address Each unit is factory preset with an address of 00 To set an SLC address refer to Setting an SLC Address for a Module on page 35 10 2 Wiring a Manual Pull Station Typical wiring for the JBG 12LX Manual Pull Station to an SLC Figure 10 1 Wiring the JBG 12LX Pull Station to an SLC US PAT 444 0991 SLC To ne...

Page 53: ... voltage of the detector or end of line relay whichever is greater in volts N total number of detectors on the 24 VDC supply circuit Is detector current in standby Na number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia detector current in alarm Ir end of line relay current Nb number of Notification Appliance Devices Ib Notification Appliance current whe...

Page 54: ... a power supervision relay This relay energized by the 24 VDC power itself is installed at the end of each respective power run and wired in line with the supervised circuit of any intelligent module When power is removed from the relay the normally closed contacts open the supervised circuit generating a trouble condition Therefore the relay needs to be installed at the end of the supervised circ...

Page 55: ...pervising 24 VDC Power Power Considerations Figure A 2 Alternate 2 Address Method of Supervising a 24 VDC Circuit M300CJ M300MJ Power Supervision Relay EOLR 1 Supervised NAC or IDC ELR 47K 24 VDC Power from Control Panel or Power Supply SLC psr 2addresstpH wmf ELR 47K ...

Page 56: ...eral alarm Refer to the programming manual or programming section of the FACP documentation for instructions Note that if the NAC is a coded output the M300CJ output will be coded as well Refer to the Device Compatibility Document for compatible notification appliances The circuit is supervised and power limited In this circuit an external ELR is required at end of the NAC circuit Refer to the res...

Page 57: ...ice Compatibility Document for compatible notification appliances The circuit is supervised and power limited In this circuit an external ELR is not required at end of the NAC circuit Refer to the respective control panel installation manual for NAC terminal block connection information Remove internal resistor on each M300CJ see instructions in Figure 7 2 on page 42 Connect the NAC power as follo...

Page 58: ...ne primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building Install primary protection only as shown in this document Refer to NEC Article 800 and local building code requirements Additional primary surge suppressors may be added as required by the NEC Add these additional suppressors in series with the SLC wiring at the building entry exit Wirin...

Page 59: ...cted in series with the SLC Loop to protect the Control Panel Provide a common ground to eliminate the possibility of a differential in ground potentials B 2 1 IFC 200 DTK 2LVLP F Connections PLP 42N Connections IN IN OUT OUT 2LVLP F 2LVLP F SLC Loop SLC Terminal Block SLC lvlp1 cdr Optional Four wire Return Loop Style 6 Class A INPUT OUTPUT PLP 42N L1 L2 L3 L4 L1 L2 L3 L4 GRND INPUT OUTPUT PLP 42...

Page 60: ...ss A IN IN OUT OUT 2LVLP F 2LVLP F SLC lvlp2 cdr SLC Loop SLC Terminal Block Optional Four wire Return Loop Style 6 Class A INPUT OUTPUT PLP 42N L1 L2 L3 L4 L1 L2 L3 L4 GRND INPUT OUTPUT PLP 42N L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn2 cdr SLC Loop SLC Terminal Block Optional Four wire Return Loop Style 6 Class A NOTE Use 12 AWG 3 31 mm2 to 18 AWG 0 82 mm2 wire with crimp on connectors to connect th...

Page 61: ...lvlp3 cdr SLC Terminal Block SLC Loop Optional Four wire Return Loop Style 6 Class A NOTE Do not connect shield if present to surge protector or fire panel INPUT OUTPUT PLP 42N L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn3 cdr SLC Terminal Block SLC Loop Optional Four wire Return Loop Style 6 Class A NOTE Use 12 AWG 3 31 mm2 to 18 AWG 0 82 mm2 wire with crimp on connectors to connect the unit s ground te...

Page 62: ...e Return Loop Style 6 Class A NOTE Do not connect shield if present to surge protector or fire panel INPUT OUTPUT PLP 42N L1 L2 L3 L4 L1 L2 L3 L4 GRND SLC plpn3 cdr SLC Terminal Block SLC Loop Optional Four wire Return Loop Style 6 Class A NOTE Use 12 AWG 3 31 mm2 to 18 AWG 0 82 mm2 wire with crimp on connectors to connect the unit s ground terminal to equipment ground Wire length must be minimize...

Page 63: ...rsions V type Terminal Number Terminal Function H type Terminal Number 1 SLC 1 2 SLC 2 3 Unused 3 4 Normally Open 1 5 5 Normally Closed 1 6 6 Relay Common 1 7 7 Normally Open 2 8 8 Normally Closed 2 9 9 Relay Common 2 10 N A Unused 4 N A Unused 11 Type V Type H Common 2 Closed 2 Open 2 Common 1 Closed 1 Open 1 SLC SLC SLC SLC Common 2 Closed 2 Open 2 Common 1 Closed 1 Open 1 ...

Page 64: ...0CJ and M302MJ Terminal Conversions V type Terminal Number Terminal Function H type Terminal Number 1 SLC 1 2 SLC 2 3 VDC 11 4 VDC 10 5 Unused 5 6 Solenoid B A 6 7 Solenoid B A 7 8 Solenoid A 8 9 Solenoid A 9 N A Unused 3 N A Unused 4 VDC VDC SLC SLC SLC SLC VDC VDC Solenoid A Solenoid A Solenoid B A Solenoid B A Solenoid A Solenoid A Solenoid B A Solenoid B A Type V Type H ...

Page 65: ...al Function H type Terminal Number 1 SLC 1 2 SLC 2 3 Unused 3 4 Unused 4 5 Unused 5 6 Class A B Supervision 6 7 Class A B Supervision 7 8 Class A Supervision 8 9 Class A Supervision 9 N A Unused 10 N A Unused 11 SLC SLC Class A Supervision Class A Supervision Class A B Supervision Class A B Supervision Class A Supervision Class A Supervision Class A B Supervision Class A B Supervision SLC SLC Type...

Page 66: ...0 F 87 8 C fixed temperature alarm DH300PL DH300PLA Photoelectric Duct Detector Low flow DH300RPL DH300RPLA Photoelectric Duct Detector Low flow FTX P1J Smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical Discontinued FTX P2J FTX P2JA Smoke detector provides early warning smoke detection in hostile environments wher...

Page 67: ...6 cm square mounting box M300RJ M300RJA Relay Control Module is similar to the M300CJ except used as a Form C control relay module Fault Isolator Module M500XJ M500XJA The Fault Isolator Module protects the system against wire to wire short circuits on the SLC It should be placed between groups of sensors in a Style 6 or Style 7 SLC to isolate short and open circuit problems and protect the rest o...

Page 68: ...7 common ground 59 communications loop 29 conduit types of 23 25 connector screw 23 connectors crimp on 60 61 62 control modules 12 Control Modules Overview 67 D DC resistance 18 degraded mode 12 33 detector bases list of 13 see also isolator bases Detectors Detector bases 66 listing 66 detectors 24 VDC 54 listing 14 devices addressable 28 auxiliary 13 isolator 28 maximum number between isolators ...

Page 69: ... 33 M300MJ 4 20 12 34 Terminal Designations 34 M300RJ see Relay modules M301MJ see miniature monitor module M302MJ see zone interface module M302MJ see zone interface module 33 M500FPJ 12 M500XJ see isolator module metal conduit 24 31 Miniature monitor module 34 module circuits configuring 33 modules addressable 12 control 12 h type 65 isolator 12 monitor 12 relay 13 v type 65 monitor module 12 33...

Page 70: ... 15 wiring 36 37 38 39 40 SLCP 30 58 sounder bases 13 28 speaker circuit 12 Sprinkler supervision 36 37 38 39 40 standard bases 13 Style 4 Style 6 Style 7 Style B Style D Style Y Style Z see NFPA Style 26 supervised circuits 54 56 supervised devices 54 suppressors surge 58 surge protector 11 58 T telephone circuit 12 terminal block NAC 57 termination of shield 23 transponders 13 trouble conditions...

Page 71: ...Johnson Controls Inc SLC Wiring Manual P N 51870 G 04 23 2009 71 ...

Page 72: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release G Printed in U S A ...

Reviews: