8.7 Setting of Control Mode
The following procedure shows the setting by CIW01.
The Indoor Temperature Control mode has been set at factory. It can be changed to Outlet Air Temperature
mode, so comply with the following instructions according to the installation conditions and purposes.
And the settings are necessary for both the indoor and outdoor unit. If either is failed to set, the Outlet Air
Temperature mode is not available. Make sure to complete both settings. (Even if either is failed to set, the
alarm does not go off.)
8.7.1 Setting of Indoor Unit by Optional Wired Controller
Turn ON the power supply (mains) and comply with the following procedure.
However, if the position of No.3 (DSW8: The Setting for Control Mode) is ON, the change of setting by
optional wired controller is not available. Make sure to check it.
'2$6FDQQRWVHW2XWOHW$LU7HPSHUDWXUH&RQWUROZKHQFRPELQHGZLWKRWKHUVWDQGDUGLQGRRUXQLWV
Factory Settings are all OFF.
DSW8 (Control Mode Setting)
1 2 3
ON
OFF
The “ ” mark indicates position of DIP switches.