background image

356485-UIM-G-1211

24

Johnson Controls Unitary Products

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

2. Motor voltage at 115 V.

Table 13: 

Blower Performance CFM - Any Position (without filter) - Bottom Return

Models

Speed

Bottom Airflow Data (SCFM)

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

040A08

High 

966 923 874 804 717 566 386 121  NA  NA 

Medium 

High  813 782 743 687 605 464 280 118  NA  NA 

Medium 

Low  745 706 667 619 545 413 205  NA  NA  NA 

Low 

684 655 614 565 489 342 171  NA  NA  NA 

060A10

High 

1292 

1230 

1160 

1088 

1004 891 760 476 129 129 

Medium 

High 1203 

1157 

1105 

1035 942 846 728 485 133 129 

Medium 

Low 1043 

1010 962 905 823 705 491 305 124 123 

Low 

869 845 811 772 708 579 438 178 145 125 

060A12

High 

1358 1341 1319 1303 1275 1238 1190 1130 1062  943 

Medium 

High  1097 1083 1075 1064 1042 1024  997  962  906  821 

Medium 

Low  935 928 920 899 872 840 809 771 731 659 

Low 

800 779 763 736 711 687 657 622 584 529 

080B12

High 

1329 1307 1285 1247 1195 1143 1091 1027  927  806 

Medium 

High  994 1004 

1008 984 970 941 893 839 773 669 

Medium 

Low  786 790 782 781 761 743 726 685 630 540 

Low 

655 654 647 629 620 594 560 524 469 399 

080C16

High 

1881 1822 1783 1696 1602 1539 1465 1394 1267 1130 

Medium 

High  1553 1535 1492 1456 1408 1343 1279 1226 1113 1014 

Medium 

Low  1312 1286 1288 1260 1205 1143 1091 1029  966  841 

Low 

1169 

1166 

1128 

1098 

1069 

1032 987 909 835 747 

080C22

High 

2811 2725 2638 2540 2448 2339 2224 2111 1974 1831 

Medium 

High  2234 2233 2147 2092 2042 1974 1907 1820 1705 1575 

Medium 

Low  1722 1716 1690 1681 1603 1553 1489 1426 1335 1241 

Low 

1396 1375 1348 1325 1263 1200 1150 1120 1052  965 

100B12

High 

1314 1318 1292 1265 1223 1177  1119 1051  971  890 

Medium 

High 1010 

1004 

1003 995 992 956 914 857 798 721 

Medium 

Low  812 805 796 786 777 754 727 685 626 560 

Low 

661 659 644 623 614 605 568 532 482 399 

100C16

High 

2069 2014 1956 1885 1820 1748 1668 1577 1468 1362 

Medium 

High  1662 1656 1639 1608 1586 1544 1491 1421 1338 1204 

Medium 

1368 1371 1377 1376 1367 1334 1295 1250 1188 1104 

Low 

1016 1014 1018 1030 1012  996  975  944  898  852 

100C20

High 

2893 2774 2687 2589 2478 2376 2255 2120 1978 1824 

Medium 

High  2272 2243 2204 2169 2086 2018 1940 1842 1743 1602 

Medium 

Low  1765 1752 1737 1718 1674 1619 1561 1493 1437 1312 

Low 

1425 1380 1409 1378 1307 1274 1226 1180  1113 1025 

120C16

High 

1752 1724 1702 1664 1600 1542 1454 1372 1264 1119 

Medium 

High  1469 1449 1453 1420 1382 1344 1269 1197  1118 1022 

Medium 

Low  1248 1235 1226 1207 1179 1133 1077  992  922  841 

Low 

1076 1076 1046 1025 1002  968  927  869  784  707 

120C20

High 

2701 2620 2533 2429 2338 2227 2112 1993 1861 1706 

Medium 

High  2125 2083 2046 1994 1955 1901 1857 1737 1621 1497 

Medium 

Low  1664 1664 1647 1619 1580 1555 1468 1392 1332 1226 

Low 

1358 1339 1330 1318 1286 1235 1185 1141 1060  938 

130D20

High 

2823 2714 2613 2507 2399 2282 2170 2042 1908 1761 

Medium 

High  2242 2188 2154 2102 2045 1970 1887 1792 1673 1537 

Medium 

Low  1805 1791 1738 1725 1675 1623 1567 1487 1394 1256 

Low 

1425 1427 1403 1335 1324 1280 1236 1176 1103  996 

Summary of Contents for GG8S*MP

Page 1: ...Position without filter Bottom Return 24 Blower Performance CFM Any Position without filter Left Side Return 25 These high efficiency compact units employ induced combustion reli able hot surface ign...

Page 2: ...binet support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings bottom or sides or supply air opening 13 When lifting the furnace it is acceptable to use th...

Page 3: ...the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NS...

Page 4: ...noxide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a batter...

Page 5: ...otated down for shipment In order to use the flanges remove the screw holding an individual flange rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4...

Page 6: ...CE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the coil is used with a furnace of a different size use a 45 transition to allow proper...

Page 7: ...will be necessary to seal the edges of the bottom panel to the casing using tape or other appropriate gasket material to prevent air leakage BOTTOM RETURN AND ATTIC INSTALLATIONS Bottom return applica...

Page 8: ...one support at the supply end of the furnace one support located approximately in the center of the furnace near the blower shelf and the third support should be at the return end of the fur nace Mai...

Page 9: ...M m3 min Cabinet Size Cabinet Dimensions Inches Approximate Operating Weights A A cm B B cm C C cm Lbs 40 11 7 800 22 7 A 14 1 2 36 8 13 3 8 34 0 10 3 26 2 89 60 17 6 1000 28 3 A 14 1 2 36 8 13 3 8 34...

Page 10: ...this section specify the type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 15 FIGURE 13 Side Return Cuto...

Page 11: ...ne LP gas must have the LoNOx screens removed prior to installation and operation See propane instructions Table 5 Nominal Manifold Pressure Manifold Pressures in wc Manifold Pressures kpa Altitude fe...

Page 12: ...ct the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module as shown in Figures 17 or 18 Electronic thermostats may require the common wire to b...

Page 13: ...ressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC Humidifier Optional C...

Page 14: ...S HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND DEFROST CONTROL X L Malfunction Light W Auxiliary Heat SINGLE STAGE HEAT PUMP 1 1 Par...

Page 15: ...he furnace that operates on W2 will be supplying cold air in the Heating mode to the occupied spaces unless W2 is energized GAS PIPING Furnace gas supplies must be provided as specified with these ins...

Page 16: ...scribed below 2 Connect a wire from the TWIN terminal of Furnace 1 to the TWIN terminal of Furnace 2 3 Install a separate 24V relay as shown in the diagram below Use of this relay is required as it en...

Page 17: ...ney must extend at least 5 ft 1 5 m above the highest equipment draft hood or flue collar FAN ASSISTED COMBUSTION SYSTEM This appliance is equipped with an integral mechanical means to either draw pro...

Page 18: ...must be given consideration in calculating free area If the free area of a specific louver or grille is not known Refer to Table 7 to estimate free area Ventilated Combustion Air The ventilated attic...

Page 19: ...simply slide the NOx screens out of the heat exchanger tubes and discard the screens 8 Replace all components in reverse order Reconnect all wiring CARBON MONOXIDE POISONING HAZARD Failure to follow t...

Page 20: ...ilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note reading The 2 cubic feet dial provides a more accurate mea sur...

Page 21: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 23...

Page 22: ...n and follow the operating instructions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following 4 After the mani...

Page 23: ...must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as...

Page 24: ...638 2540 2448 2339 2224 2111 1974 1831 Medium High 2234 2233 2147 2092 2042 1974 1907 1820 1705 1575 Medium Low 1722 1716 1690 1681 1603 1553 1489 1426 1335 1241 Low 1396 1375 1348 1325 1263 1200 1150...

Page 25: ...ow 1126 1115 1095 1049 1027 996 957 929 840 742 080C22 High 2972 2863 2769 2671 2571 2465 2352 2227 2095 1950 Medium High 2173 2146 2103 2082 2036 1966 1904 1827 1738 1621 Medium Low 1670 1667 1647 16...

Page 26: ...ion occurs and the flame sensor begins its sensing function The blower motor will energize 30 seconds after the gas valve opens if a flame is detected Normal furnace operation will continue until the...

Page 27: ...ed Flashes description below If the main limit switch opens five times within a single call for heat the control will also indicate 4 Red Flashes and will enter a one hour soft lockout 5 RED FLASHES T...

Page 28: ...ill flash three green flashes when the memory has been cleared then will resume the normal slow green flash after a five second pause SECTION X REPLACEMENT PARTS LIST DESCRIPTION MOTOR MOTOR DIRECT DR...

Page 29: ...lower motor speed connections shown are typical but may vary by model and application LEGENDE DS Commutateur de porte MOT Moteur soufflerie TST Thermostat ROS Commutateur de roulement IDM D induct mot...

Page 30: ...ge without notice Published in U S A 356485 UIM G 1211 Copyright 2011 by Johnson Controls Inc All rights reserved Supersedes 356485 UIM F 0910 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: