Johnson Controls G861 Series Technical Bulletin Download Page 3

G—G861 Series Integrated Function Direct Spark Ignition Control Technical Bulletin    3

The following conditions occur in normal control operation:

 

Prepurge--Initial time delay between thermostat contact closure and
trial for ignition.

 

Trial-for-Ignition Time--Maximum time period that the main gas valve
and igniter energizes in an attempt to light the main burner.

 

Interpurge--Time period between trials for ignition when both the gas
valve and ignition source turn off and the inducer is on, allowing
unburned gas to escape before a succeeding trial can occur. (Retry takes
place only if proper ignition did not occur during the previous trial and
if total trials are less than three.)

 

Run--Main gas valve remains energized after a successful ignition trial.

 

Circulator/Blower “On Delay”--Fixed time delay after the flame is
sensed until the circulator/blower is energized.

 

Circulator/Blower “Off Delay”--Field selectable time delay after the
thermostat contacts open when the circulator/blower remains energized.

 

Postpurge--Time delay after the thermostat is satisfied when the
inducer remains energized.

Figure 2 illustrates the sequence of operation of the G861 control.

Upon receiving a call for heat from the system thermostat, the G861
follows this normal sequence of operation:

1.

 

Pressure Switch Detection--The control checks the inducer pressure
switch to ensure that it is open.

2.

 

Prepurge--The control energizes the inducer motor and verifies that the
pressure switch closes.

3.

 

Pressure Switch Detection--The control checks the pressure switch to
ensure that it remains closed during the prepurge period.

4.

 

Trial for Ignition--The control simultaneously energizes the spark
igniter and gas valve in an attempt to light the main burner. During the
trial time, the igniter is energized until flame is detected or until the
trial for ignition is complete, whichever occurs first.

5.

 

Run--If main burner flame is sensed up to the last 0.5 second of the
trial, the gas valve and inducer remain energized for the duration of the
heat call. The circulator/blower is energized after a 30-second blower
“on delay” time and remains energized for the duration of the heat call.

6.

 

Postpurge--Once the thermostat is satisfied, the gas valve is
de-energized and the inducer remains energized until the postpurge
period ends. The circulator/blower remains energized until the selected
blower “off delay” time has elapsed.

Operating
Mode
Definitions

Normal
Sequence of
Operation

Call for Heat

Summary of Contents for G861 Series

Page 1: ...nsor It provides outputs for timing and sequencing of the main gas valve induced draft motor circulator blower and spark igniter The G861 utilizes quick connect terminals for all off board connections except thermostat inputs and spark output The thermostat inputs are connected to a terminal strip with screw terminals and the spark output is connected by a rajah spike or 1 4 in male tab type spark...

Page 2: ...ontrol 24 VAC 50 60 Hz nominal Operation Current 0 3A 24 VAC Contact Rating Main Valve 2A continuous at 24 VAC 5A inrush Inducer 2A continuous 120 VAC Blower 1 3 hp 7 20 FLA 125 VAC Ambient Operating and Storage Temperature 40 to 70 C 40 to 160 F Humidity 95 RH non condensing Wiring Connections Spark Spike rajah or 1 4 in male tab Types of Gas Natural Liquefied Petroleum LP manufactured mixed or L...

Page 3: ...of operation of the G861 control Upon receiving a call for heat from the system thermostat the G861 follows this normal sequence of operation 1 Pressure Switch Detection The control checks the inducer pressure switch to ensure that it is open 2 Prepurge The control energizes the inducer motor and verifies that the pressure switch closes 3 Pressure Switch Detection The control checks the pressure s...

Page 4: ...No Postpurge No End Thermostat calls for m anual fan G No Run manual fan speed Thermostat call for heat Pressure switch open Yes Retry mode 60 m inute delay No Yes Pressure switch closed Third trial Trial for ignition Sixteenth flameout Flam e sensed Circulator Blower on delay Thermostat satisfied Circulator Blower off delay field selectable Figure 2 G861 Sequence of Operation ...

Page 5: ...ill immediately de energize the gas valve If the pressure switch fault occurs after the flame is sensed the circulator blower will run for 90 seconds the inducer motor will remain energized and the control will go into the Pressure Switch Open Fault state During this time the LED will blink with a flash code of 3 As long as the call for heat is still present the control will continue to wait for t...

Page 6: ...rmostat will run the circulator blower at medium speed During the 60 minute retry delay period the LED will blink with a flash code of 2 A manual fan call from the thermostat during the 60 minute retry will run the circulator blower at medium speed The G861 offers the following responses to the two possible interrupted thermostat situations If the call for heat is removed before the gas valve is e...

Page 7: ... If the control is installed in an area that is exposed to water dripping spraying rain etc it must be protected If the control has been exposed to water in any way do not use it WARNING Shock Hazard Avoid electrical shock and equipment damage Disconnect the electrical power and turn off the gas before wiring the control into the circuit Choose a location that provides the shortest direct cable ro...

Page 8: ... transformer having excessive primary impedance due to poor coupling will affect the ignition potential Refer to Figure 3 for the G861 wiring diagram All wiring should be in accordance with the National Electrical Code NEC and all other local codes and regulations The high voltage spark transformer cable must not be in continuous contact with a metal surface Use standoff insulators Ensure that the...

Page 9: ...rm e r 24 V L in e 2 4 V C o m m o n S p ark Tra n s fo rm er 24 VA C H o t G ro u nd F lam e S e n se P S W P re s s u re S w itc h H ig h L im it In H igh L im it O ut R o llo u t In B lo w e r O ff D e la y S etting H igh L im it S w itc h R o llo ut S w itc h T he rm o s ta t 3 1 6 in ch Te rm in a l W G R S e nso r N ote A ll term in a ls are 1 4 in ch u n less o the rw ise spe cified P re ss...

Page 10: ...nd verify that the control goes through the operating sequence to a shutoff condition Note The burner will not light because the gas is off 3 Turn the thermostat off 4 Turn gas on and purge gas lines of all air 5 Check for gas leaks on all pipe joints upstream of the gas valve with a soap solution 6 Turn the thermostat to a high setting and verify successful ignition and a normal run condition for...

Page 11: ...draw of the heating system at the thermostat location Measuring this current can be accomplished by opening the thermostat contacts lowering the setpoint and installing an AC ammeter across the terminals or by using a clamp on ammeter with a 10 turn multiplier attached to the terminals See Figure 4 Ten Turns Clamp on Ammeter Divide reading by ten W R W R AC Ammeter Low Scale Setting To Heating Sys...

Page 12: ...ash Three Pressure switch open or closed Flash Four High limit open Flash Five Flame sensed and gas valve not energized Steady On Internal failure microcontroller self check failure CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Do not attempt field repairs to the ignition control Use only an exact or recommended repl...

Reviews: