10 G—G861 Series Integrated Function Direct Spark Ignition Control Technical Bulletin
!
WARNING:
Fire or Explosion Hazard. Avoid personal injury
or property damage by making sure the control
functions properly and there are no gas leaks.
Follow this checkout and startup procedure before
leaving the installation.
Make sure all components function properly by performing the following
shutoff test:
1.
With the gas and thermostat off, turn on power to the appliance.
2.
Turn the thermostat to a high setting and verify that the control goes
through the operating sequence to a shutoff condition.
Note: The burner will not light because the gas is off.
3.
Turn the thermostat off.
4.
Turn gas on and purge gas lines of all air.
5.
Check for gas leaks on all pipe joints upstream of the gas valve with a
soap solution.
6.
Turn the thermostat to a high setting and verify successful ignition and
a normal run condition for at least three minutes.
7.
Check for gas leaks on all pipe joints downstream of the gas valve with
a soap solution.
8.
Turn the thermostat down for at least 30 seconds, and then back up
again. Verify successful ignition at least three times before leaving the
installation.
Checkout and
Startup
Procedures