Note: 

Do 

not

 connect a controller with switch 128 set to ON to an active (hard-wired) SA or

FC bus. When a controller with switch 128 set to ON and a device address from 4 to 127 is

connected to a wired field bus, the entire field bus is rendered inoperable until the controller is

disconnected or switch 128 is set to Off.

Refer to the 

FX-ZFR Series Wireless Field Bus System Technical Bulletin (LIT-12011660)

 for more informa-

tion on device addresses in wireless applications.
4. Set a unique and sequential device address for each of the controllers connected on the SA or

FC bus starting with device address 4.

To ensure the best bus performance, set sequential device addresses with no gaps in the device

address range (4, 5, 6, 7, 8, 9, and so on). The controllers do 

not

 need to be physically connected on

the bus in their numerical device address order.
5. Write each controller's device address on the white label below the DIP switch block on the

controller's cover.

Table 6 describes the FC bus and SA bus devices addresses for Johnson Controls MS/TP communica-

tions bus applications.
Refer to the 

FX-PC Series ControllersMS/TP Communications Bus Technical Bulletin (LIT-12011670)

 or 

MS/

TP Communications Bus for BCPro System Technical Bulletin (LIT-12011908)

 for more information on

controller device addresses and how to set them on MS/TP buses.

Table 6: SA/FC bus device address descriptions

Device address

Use on description

0

(Switch 128 Off)

Reserved for FC Bus Supervisory Controller (not for use on controllers).

1 to 3

(Switch 128 Off)

Reserved for peripheral devices (not for use on controllers).

4 to 127

(Switch 128 Off)

Used for MS/TP master devices (controllers) that are hardwired to an SA Bus

or FC Bus.

0 to 3

(Switch 128 ON)

Reserved addresses for wired subordinate devices (not for use on controllers).

Note: 

FX-PC controllers ship with switch 128 ON and the remaining

address switches off rendering the controllers wired subordinate devices,

which do not operate on MS/TP buses.

4 to 127

(Switch 128 ON)

Valid for MS/TP Master controllers on 

wireless FC Buses only

.

Note: 

Do 

not

 connect a controller with switch 128 ON to an active (

hard-

wired

) SA or FC bus. When a controller with switch 128 ON and a device

address from 4 to 127 is connected to a wired field bus, the entire field

bus is rendered inoperable until the controller is disconnected or switch

128 is set to Off.

Removing the Controller cover

About this task:

23

FX-PCX17 and FX-PCX27 Expansion Input/Output Module Installation Instructions

Summary of Contents for FX-PCX17 Series

Page 1: ...ng Equipment Regulations Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada United States This equipment has been tested and found to...

Page 2: ...evenly on the mounting surface Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in Technical specifications Provide for sufficient space around...

Page 3: ...inst the DIN rail 4 Push the bottom mounting clip inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bottom mounting clip out to the extended posi t...

Page 4: ...o the holes or wall anchors Carefully tighten all of the screws Important Do not overtighten the mounting screws Overtightening the screws may damage the mounting clips Mounting Features and Dimension...

Page 5: ...PCX17 See Table 3 for more information 7 End of Line EOL Switch See Setting the End of Line EOL switch for more information Note The EOL Switch is located under the controller cover You must remove t...

Page 6: ...lectrique et de provoquer des blessures graves voire mortelles CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly co...

Page 7: ...le 3 for more information about I O terminal functions requirements and ratings SA FC bus terminal block An FX PCX can be connected to a Sensor Actuator SA bus or a Field Controller FC bus but not to...

Page 8: ...of the controller is an RJ 12 6 position modular jack that provides a connection for devices on the SA bus a Bluetooth Commissioning Converter an FX ZFR ZFR Pro Wireless Router depending on which bus...

Page 9: ...d back through the center opening as shown in the following figure Locate the ferrite ring as near to the supply power terminal plug as possible while still allowing for a typical connection to the co...

Page 10: ...er to the FC bus port RJ 12 modular jack on the front of the controller 2 Ensure that the controller s device address DIP switches are set to the correct device address See Setting the device addresse...

Page 11: ...Input Internal Source UI Voltage Input Self Powered UI Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External...

Page 12: ...cremental Control to Actuator Switch Low External Source UO 24 VAC Binary Output Switch Low Externally Sourced UO 24 VAC Binary Output Switch High Externally Sourced UO Incremental Control to Actuator...

Page 13: ...nation diagrams 4 20 mA Output to Actuator UO Voltage Analog Output UO 4 20 mA Output to Actuator UO 0 10 VDC Output to Actuator External Source UO 0 10 VDC Output to Actuator Internal Source UO 13 FX...

Page 14: ...ines in Table 3 observe these guidelines when wiring controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wir...

Page 15: ...t Mode 4 20 mA Internal 100 ohm load impedance See Guideline B in Table 4 Analog Input Resistive Mode 0 600k ohm Internal 12 V 15k ohm pull up Qualified Sensors 0 2k ohm potentiometer RTD 1k Nickel Jo...

Page 16: ...mum pulse width Internal 18 V 3k ohm pull up INn Binary Input Pulse Counter Accumulator Mode 0 01 second minimum pulse width 50 Hz at 50 duty cycle Internal 18 V 3k ohm pull up BINARY Inputs FX PCX17...

Page 17: ...nalog Output Current Mode 4 20 mA Requires and external load between 0 and 300 ohm Note The Analog Output AO operates in the Current Mode when connected to devices with impedances less than 300 ohm De...

Page 18: ...to OUT NC when activated UL Listed 0 model only 1 4 hp 120 VAC 1 2 hp 240 VAC 360 VA Pilot Duty at 120 240 VAC B300 3 A Non inductive 24 240 VAC CE Marking 2 model only 6 4 A N O or N C only 240 VAC T...

Page 19: ...mm 24 AWG stranded copper 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for t...

Page 20: ...ble 5 observe these guidelines when wiring an SA or FC bus and the 24 VAC supply power Run all low voltage wiring and cables separate from high voltage wiring All SA and FC bus cables regardless of wi...

Page 21: ...ne twisted pair and the COM and SA PWR are the second twisted pair of wires SA FC BUS Port RJ 12 6 Position Modular Connector provides FC or SA Bus Communications FC or SA Bus Signal Reference and 15...

Page 22: ...ing address switches off rendering the controllers wired subordinate devices which do not operate on MS TP buses but will not interfere with bus operation Set a valid and unique device address on the...

Page 23: ...chnical Bulletin LIT 12011670 or MS TP Communications Bus for BCPro System Technical Bulletin LIT 12011908 for more information on controller device addresses and how to set them on MS TP buses Table...

Page 24: ...ace your fingernails under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 P...

Page 25: ...terminating device on the bus set the EOL switch to Off When a controller is connected to power with its EOL switch set to ON the amber EOL LED on the controller cover is lit Commissioning the Control...

Page 26: ...n normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Communication lost waiting to join communication ring EOL Amber Off Except on terminating devices On Steady...

Page 27: ...cks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 ZFR USBHA 0 USB Dongle with ZigBee Driver provides a wireless connection through CCT t...

Page 28: ...ommunications Bus BACnet MS TP RS 485 3 wire FC Bus between the supervisory controller and other controllers 4 wire SA bus between controller network sensors and other sensor actuator devices includes...

Page 29: ...mount preferred or screw mount on flat surface with three integral mounting clips on controller Housing Enclosure material ABS and polycarbonate UL94 5VB Self extinguishing Plenum Rated Protection Cla...

Page 30: ...PCX2711 0 Europe Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EC Directive Note Except FX PCX2711 0 Australia and N...

Reviews: