IDC2 EVAPORATIVE CONDENSERS
INSTALLATION
140.940-IOM (DEC 13)
Page 4
Figure 2 - Upper Section Multi-piece Lift
NOTICE
For weight information, refer to submittal drawing package.
NOTICE
Any motors or accessories shipped in the cold water basin
must be removed prior to installing the upper section.
WARNING
In the event of extended lifts or where hazards exist, the
lifting devices should be used in conjunction with safety
slings placed under the unit.
Model Number
H (distance from lift point to
lifting device in feet)
Lower Section
Upper Section/
Single Piece Lift
IDC2-X-0406-X
14
9
IDC2-X-0412-X
16
9
IDC2-X-7409-X
14
10
IDC2-X-7418-X
16
15
IDC2-X-1012-X
16
15
IDC2-X-1212-X
16
13
IDC2-X-1218-X
18
15
Table 1 - Recommended Vertical Dimension
Most IDC2 Evaporative Condensers (Except Models IDC2-x-
1218-x) are designed to be lifted in one assembled piece as
shown in
Figure 1
. The multipiece lift is shown in
Figures 2
and
3
.
SECTION ASSEMBLY OF TWO-PIECE CELLS
•
Position the lower section on the supports and bolt in place.
•
Wipe moisture and dirt from the perimeter flange.
•
Remove any motors or accessories shipped in the cold water
basin.
•
Install sealer tape supplied with the unit, as illustrated in
Figure 4 - Mechanical Section Bolt Assembly
, on the mat-
ing flanges of the lower section in a continuous line. At each
corner, allow 1” overlap.
•
Using drift pins in the bolt holes provided, as shown in
Figure 5
, guide the upper section onto the lower section
starting with the bolt hole at one corner and follow down
the flange.
•
Screw in place using the self-tapping screws, supplied with
the unit, to ensure leak-free operation (
Figure 5a
).
SECTION ASSEMBLY OF OPTIONAL
THREE-PIECE CELLS
NOTICE
IBC Rating is void if section assembly is not performed as
described in this manual.
NOTICE
All piping must be restrained to ensure no vertical or
horizontal movement. All piping and supports are to be
furnished by others. Refer to the certified drawing for
details on the connection size, etc.
Figure 1 - Single Piece Lift