background image

IDC2 EVAPORATIVE CONDENSERS

MAINTENANCE

140.940-IOM (DEC 13)

Page 13

MAINTENANCE

COLD WATER BASIN

The refrigerant to be condensed is circulated inside the tubes of 
the unit’s heat exchanger. Heat flows from the refrigerant through 
the coil to the spray water outside which is cascading over the 
tubes. The spray water collects in the cold water basin, passes 
the suction strainer and is pumped back to the distribution sys-
tem. The cold water basin is constructed from galvanized steel. 

Water Levels

Model Number

At Overflow 
Level (in.)

At Operating 
Level (in.)

All­IDC2­models­except­
IDC2-x-1218-x

11¾”

9”

IDC2-x-1218-x

13½”

10½”

Table 2 - Cold Water Basin Water Levels

  The  makeup  valve  controls  the  operating  level,  which  is 

maintained at the levels shown in 

Table 2

.

  The operating water level in the cold water basin will vary 

with system thermal load (evaporation rate), the bleed rate 
employed, and the makeup water supply pressure.

  Check the operating water level monthly, and readjust the 

float when necessary to maintain the recommended operat-
ing level.

Inspection & Maintenance

 

WARNING

Openings and/or submerged obstructions may exist in the 
bottom of the cold water basin. Use caution when walking 
inside the equipment.

  Inspect the cold water basin regularly. Remove trash or debris 

accumulated in the basin or on the strainer.

  Quarterly or more often if necessary, drain, clean, and flush 

the entire cold water basin with fresh water. This will remove 
the sediment, which can collect in the basin during operation. 
If not removed, sediment can become corrosive and cause 
deterioration of the protective finish of metallic basins.

  When flushing the basin, leave the strainer in place to prevent 

the sediment from re-entering the system.

  Remove the strainer after the basin has been flushed.

  Clean and replace the strainer before refilling the basin with 

fresh water.

  Adjust the float to maintain the design operating level. See 

Table 1

.

FAN

The IDC2 Evaporative Condenser uses axial fan(s). Thoroughly 
inspect  the  fan  for  damaged  or  deteriorated  fan  blades  and 
replace the fan as required.

Inspection & Maintenance

  If the unit is already in operation, while the fan is running, 

check for any unusual noise or vibration.

  With the fan off and the motor locked out and tagged, check 

the general condition of the fan:

  -   Inspect  for  any  loose  or  missing  bolts  in  the  fan  shaft 

bushing, the fan hub, and the fan shaft bearing(s).

  -  Check the fan blades for looseness, first by twisting the 

blade by hand, and then by moving the blade tip up and 
down. There should be no play or slippage.

  -  Inspect each blade for excessive scale build-up that could 

cause vibration.

  -  Check each blade in the area of the shank for any signs 

of cracking. If cracking is found, the fan motor should be 
locked out immediately. Contact Johnson Controls-Frick 
or your local Frick Factor for assistance.

 

Tip Clearance

: Check the clearance between the tip of the 

blade and the fan cowl. The clearance should be between 
1/8” and 1/2”.

 

Drain Holes

: On hollow blades, the drain hole in the blade 

tip should be unobstructed. Tip: Use a piece of wire to probe 
the hole.

 

Blade Pitch

: Check to ensure that the blades are all at the 

same pitch. If uncertain, measure the pitch with an inclinom-
eter. All blades should be /-1/2°.

 

Rotation

: Turn the fan by hand to ensure that it moves freely 

with no rough spots, binding or other malfunctions that could 
cause vibration or fan motor overload. While rotating the 
fan, check the blade tracking. All blades should track within 
a 1/2” band at any single point around the cowl.

 

Direction of Rotation

: On initial start-up, or if the fan motor 

has been rewired, bump the fan motor and note the direction 
of rotation. It should rotate in the direction indicated by the 
arrow on the fan cowl.

 

Operation

:  On  initial  start-up,  run  the  fan  in  the  manual 

position for several minutes and check for any unusual noises 
or vibration.

FAN DRIVE SYSTEM

Fortitude™ Power Train

The Fortitude™ Power Train consists of a solid-backed, multi-
groove, neoprene/polyester belt rated for evaporative condenser 
service,  and  corrosion-resistant  sheaves.  These  components 
provide high reliability with low maintenance requirements.

Inspection & Maintenance

Fortitude™

 

Power  Train  requires  a  periodic  check  of  the  belt 

condition and, when necessary, tension adjustment. The recom-
mended service intervals are as follows:

•  Initial Start-Up

  -  No  servicing  is  required  prior  to  initial  start-up  since 

the drive has been tensioned and aligned at the factory. 
[IDC2-x-1212-x and IDC2-x-1218-x]

Summary of Contents for Frick IDC2

Page 1: ... IDC2 Evaporative Condenser THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJURY OR DEATH DAMAGE TO THE UNIT OR IMPROPER OPERATION Please check www jci com frick for the latest version of this publication ...

Page 2: ...Extended Shutdown 12 MAINTENANCE Cold Water Basin 13 Water Levels 13 Inspection Maintenance 13 Fan 13 Inspection Maintenance 13 Fan Drive System 13 Fortitude Power Train 13 Inspection Maintenance 13 Fan Motors 15 Model Specific Fan Drive System Descriptions 15 Inspection and Maintenance 15 Adjustable Motor Base 15 Fan Shaft Bearings 15 Inspection Maintenance 15 Water Distribution System and Heat T...

Page 3: ... operation Shims should not be used between the basin and support beams to level the unit WARNING Operation maintenance and repair of this equipment should be undertaken only by personnel qualified to do so Proper care procedures and tools must be used in handling lifting installing operating maintaining and repairing this equipment to prevent personal injury and or property damage WARNING Adequat...

Page 4: ...wn in Figures 2 and 3 Section Assembly of Two Piece Cells Position the lower section on the supports and bolt in place Wipe moisture and dirt from the perimeter flange Remove any motors or accessories shipped in the cold water basin Install sealer tape supplied with the unit as illustrated in Figure 4 Mechanical Section Bolt Assembly on the mat ing flanges of the lower section in a continuous line...

Page 5: ...crews in each hole from the mechanical section into the middle section and tighten Assembly of Multi Cell Units NOTICE On quad cell installations it is suggested that cells sub sequent to the first have the upper and lower sections assembled on the support foundation adjacent to the final mounting locations This will allow space for securing the upper and lower sections of each cell Slide the subs...

Page 6: ...ure to press the two ends together to form a smooth continuous strip Apply a second layer of sealer tape over the first layer following the same procedure Using drift pins to align the bolt holes place the flume box over the opening in the basin of Cell 1 and fasten into place Insert the 3 8 self tapping screws or bolts from the flume box into the basin wall as illustrated in Figure 6 Apply sealer...

Page 7: ... that the fan guard is properly installed prior to com mencing operation NOTICE All other IDC2 models have the fan motor mounted and tensioned at the factory Attach lifting strap to the motor base eyelet and remove the motor and motor base assembly from the cold water basin ship ping location The motor assembly remains vertical to maintain proper alignment during installation Lift assembly into po...

Page 8: ...e opening in the cold water basin and attach it to the basin with 3 8 x 1 bolts nuts flat washers and lock washers as shown in Figure 10 Detail A Place the suction strainer over the opening Platform and Ladder Installation Remove platform and ladder assembly from cold water basin Hang preassembled platform by inserting top guide pins into the fan deck notches as shown in Figure 11 Detail A Secure ...

Page 9: ...ents of the recirculating water system must wear respiratory protec tion equipment approved for such use by governmental occupational safety and health authorities WARNING The basin heater is not designed to prevent icing during unit operation Warranties Please refer to the Limitation of Warranties in the submit tal packet applicable to and in effect at the time of the sale purchase of these produ...

Page 10: ...quipment and absorbed by the recirculating water to form a corrosive solution Water The most harmful conditions develop as water evaporates from the equipment leaving behind the dissolved solids originally contained in the makeup water These dis solved solids may be either alkaline or acidic and as they are concentrated in the circulating water can produce scaling or accelerated corrosion The exte...

Page 11: ...perating freely Start up WARNING Check to ensure the controls for the fan motor are set to allow a maximum of six on off cycles per hour to prevent motor overload WARNING Pressure greater than 10 0 psig may cause damage to the distribution system Prior to seasonal start up lubricate the motor base adjusting screw s see Figures 3a and 3b and fan shaft bearings At initial start up no bearing lubrica...

Page 12: ...turer s guidelines before loading unloading weight from the unit Drain the cold water basin and all the piping that will be exposed to freezing temperatures Heat trace and insulate all exposed piping Clean all the debris such as leaves and dirt from the interior and exterior of the unit Leave the cold water basin drain open so rain and melting snow will drain from the unit Clean the basin strainer...

Page 13: ...nning check for any unusual noise or vibration With the fan off and the motor locked out and tagged check the general condition of the fan Inspect for any loose or missing bolts in the fan shaft bushing the fan hub and the fan shaft bearing s Check the fan blades for looseness first by twisting the blade by hand and then by moving the blade tip up and down There should be no play or slippage Inspe...

Page 14: ...eafter check the belt condition monthly and adjust tension as necessary Readjust tension at least once every three months Belt tension check Place a straight edge along the belt from sheave to sheave as shown in Figure 14a or use a tape measure as shown in Figure 14b to measure belt deflection Apply a moderate force by hand approximately 40 lb 275 kPa evenly across the width of the belt in the cen...

Page 15: ...ron SRI Citgo Polyurea MP2 Conoco Polyurea 2 Exxon Polyrex EM Exxon Unirex N MobilGrease AW2 Shell Alvania RL3 Shell Alvania 3 Shell Dolium R SKF LGHP2 Unocal 76 Unilife Grease NOTICE List of brand names is for identification only and are not exclusive recommendations Lubricate the bearings as follows Initial Start up Normally no lubrication is required since the bearings have been lubricated at t...

Page 16: ...g pump during system start up and provides sufficient excess basin capacity to accept the total system pull down volume Optional Electric Water Level Control Package As an option an electric water level control package is avail able in lieu of the mechanical makeup assembly The package consists of a probe type liquid level control assembly and a slow closing solenoid valve Stainless steel electrod...

Page 17: ... motor voltage and current X X Clean fan motor exterior X X Check fan motors for proper rotation X Check fans for rotation without obstruction X X Check general condition of the fan X Check and unplug fan drain holes hollow blade fans X Check fan for uniform pitch X Check and recoat steel shafts with RUST VETO X X X 1 Recommended service intervals are for typical installations Different environmen...

Page 18: ...IDC2 EVAPORATIVE CONDENSERS NOTES 140 940 IOM DEC 13 Page 18 ...

Page 19: ...IDC2 EVAPORATIVE CONDENSERS NOTES 140 940 IOM DEC 13 Page 19 ...

Page 20: ...boro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www jci com frick Form 140 940 IOM 2013 12 Supersedes 140 940 IOM 2013 02 Subject to change without notice Published in USA 01 15 PDF 2015 Johnson Controls Inc ALL RIGHTS RESERVED ...

Reviews: