100.210-IOM (FEB 2015)
Page 7
VYPER
™
VARIABLE SPEED DRIVE
INSTALLATION - OPERATION - MAINTENANCE
--.Apply.power.to.the.Vyper.Drive.system..
.
A:. Confirm.dipswitches.on.the.Vyper.Logic.Board.are.properly.set..Refer.to.“VSD.Logic.Board.Setup”.in.the.OPERATION.
section.of.this.manual.
.
B:. Verify.no.problems.exist.with.the.unit.power.supply.connections.
.
C:. Verify.no.problems.exist.with.the.boot-up.of.the.Quantum
™
LX.panel.and.control.system.
.
D:. Set.the.FLA.ratings.on.the.Vyper.Logic.Board.as.per.job.site.requirements.
.
E:. Set.up.the.Quantum
™
LX.panel.in.accordance.with.job.site.requirements..Refer.to.“Quantum
™
LX.Panel.Setup”.in.the.
OPERATION.section.of.this.manual.
.
F:. Confirm.operation.of.internal.cooling.fans.
.
G:. Confirm.operation.of.the.coolant.pump.
.
h:. Confirm.operation.of.the.Vyper.motorized.coolant.temperature.control.mixing.valve..
.
I:. Confirm.wiring,.operation,.and.correct.rotation.of.motor.blower.fans.if.present.
Pre-Startup Inspection
After.installation.is.complete,.use.the.following.as.guide.to.
checks.items.D.–.I,.under.in.the.Applying.power.to.the.Vyper
™
.
Drive.system.section,.in.the.preceding.Vyper
™
.Pre-Operation.
Site.Checklist..Any.changes.to.factory.setpoints,.needs.to.
be.approved.by.Frick
®
..Failure.to.obtain.approval.may.void.
warranty..Read.all.steps.thoroughly.and.contact.the.factory.
with.any.questions.before.proceeding..
1.. With.power.off.-.In.the.drive,.remove.wire.624.(com-
pressor.run).on.the.drive.side.of.control.wiring.terminal.
strip..
2.. Remove.wire.675.(oil.pump.run).if.the.unit.is.equipped.
with.an.oil.pump.
3.. Close.the.drive,.turn.on.the.disconnect.using.the.operat-
ing.handle.on.the.door.
4.. Once.the.Quantum
™
LX.panel.has.booted.go.to.the.level.
2.operating.session.
5.. Confirm. communications. between. the. Vyper
™
. drive.
and.the.Quantum
™
LX.by.going.to.the.Vyper
™
.screen..
If.there.are.base-plate.temperature.readings.that.are.
approximate.to.ambient.and.a.value.is.displayed.for.the.
JOB.FLA.communications.is.confirmed..Compare.the.Job.
FLA.value.to.the.panel.test.report.Special.Instructions.
section.to.ensure.they.match..If.the.JOB.FLA.is.not.listed.
on.the.panel.test.report,.use.the.JOB.FLA.tables.in.this.
manual.to.calculate.
6.. Go.to.the.motor.setpoints.screen.to.check.the.motor.
amps.safeties,.relative.to.the.motor.and.drive.combina-
tion..If.these.values.are.not.correct.use.the.tables.in.this.
manual.to.calculate.what.they.should.be.
7.. Verify.proper.operation.of.the.motorized.coolant.mixing.
valve.on.the.back.of.the.drive..
.
•.
Locate.the.Coolant.mixing.valve.on.the.back.of.the.
drive,.remove.the.cover.from.the.motor.and.check.
that.the.dip-switches.are.set.as.1.ON,.2.OFF,.3.ON.
&.4.OFF..If.a.change.needs.to.be.made,.the.power.
must.be.cycled.at.the.panel.for.the.change.to.be.in.
effect..
.
•.
Go.to.Page.2.of.PID.setpoints,.for.the.Vyper.Coolant.
PID..Ensure.the.setup.is.per.the.setup.in.this.manual..
If.it.is,.set.the.Control.as.Always.and.the.Direction.
as.Reverse..Check.the.indicator.disc.or.arrow.on.
the.shaft.between.the.valve.and.the.actuator.motor.
that.it.is.operating..Once.it.has.moved.to.one.end.of.
the.stroke,.change.the.Direction.back.to.Forward..
This.should.move.the.Indicator.Disc.or.Arrow.back.
to.the.other.end.of.the.stroke..
.
•.
Set.the.Control.back.to.Running.and.submit.
8.. Using. a. screw. driver. at. the. operating. handle. on. the.
door,.open.the.drive.leaving.the.power.on,.so.that.the.
ride.side.panel.can.be.opened.providing.access.to.the.
logic.board.
9.. Re-secure.the.left.side.panel.
10.. If.the.Job.FLA.setting.is.not.correct.this.can.now.be.set.
using.the.Job.FLA.pot.on.the.control.logic.board..Moni-
tor.the.value.on.the.Vyper.screen.of.the.Quantum
™
LX.
to.determine.when.the.value.is.properly.set.
11.. Test.the.internal.fan.and.coolant.circulation.pump.op-
eration.by.removing.the.P2.plug.from.the.J2.connector.
on.the.control.logic.board..Removing.this.plug.will.start.
these.devices..You.will.hear.the.fans.run..The.circula-
tion. in. the. coolant. loop. should. be. seen. through. the.
clear. hose,. proving. the. circulation. pumps. operation..
Reconnect.the.P2.plug.to.the.J2.connector.to.turn.off.
these.devices..Doing.this.test.will.create.a.Low.Inverter.
Base-Plate.Temperature.shutdown.on.the.Quantum
™
LX.
that.will.need.to.be.cleared.
12.. Close.the.drive.completely.and.with.power.still.on,.do.a.
simulated.run.of.the.compressor.by.pressing.the.manual.
start.button.on.the.Quantum
™
LX..This.should.engage.
the.blower.motors.on.the.compressor.drive.motor.to.
verify.proper.rotation.and.operation.of.the.blower.mo-
tors..Rotational.arrows.on.the.fan.housing.shows.proper.
rotation,.correct.if.necessary.by.changing.any.two.wires.
at.the.blower.motor.connection.box.with.power.locked.
out.
13.. Turn.power.off.with.the.operating.handle.on.the.door.
of.the.drive..Open.the.drive.and.check.to.ensure.the.
panel.is.de-energized..Carefully.replace.wires.624.and.
675..Tighten.to.12.lb..In.