100.210-IOM (FEB 2015)
Page 46
VYPER
™
VARIABLE SPEED DRIVE
OPERATION
PROGRAMMING PID SETUP
Step 1:
(See. Figure. 46). The. PID. Setup. Screen. requires.
programming. so. that. the. Quantum
™
LX. panel. will. control.
the. cooling. system. for. the. Vyper
™
. Drive.. Advance. to. the.
PID.Setpoints.Screen.by.pressing.the.[
MENU
].key.and.then.
selecting.“
Setpoints
”,.“
PID Setup
”,.and.“
Page 2
”..
Step 2:
(See.Figure.46).Use.the.cursor.arrow.and.[
Tab
].keys.
to.navigate.between.setpoints..With.the.keypad,.program.
the.parameters.listed.in.Table.13.under.“PID.#5”.on.the.PID.
Setup.Screen..Press.the.[
Enter
].key.to.accept.each.setpoint.
Figure 46 - PID Setup Screen (Page 2)
TABlE 13 – PID CHAnnEl #5 SETPoInTS
PID Parameter
Value
Name
Drive.Cooling
Control
Running
Action
Forward
Control.Point
Vyper
™
Coolant*
Device.Source
Analog.Board.2
Device.Channel
1
Setpoint
100°F
Dead.Band
0.0°F
Proportional.Band
20°F
Integration.Time
30
high.Limit
100%
Low.Limit
0%
When.Running.OFF.Value
0%
Step 3:
Press.the.[
Submit
].key.to.accept.the.changes.to.PID.
Channel.5.and.return.to.the.operating.status.screen.