background image

Figure  9: Device address DIP switch block set to

address 21

Note: 

 

Metasys

 field controllers ship with switch

128 ON and the remaining address switches off

rendering the controllers wired subordinate devices,

which do not operate on MS/TP buses, but will not

interfere with bus operation. Set a valid and unique

device address on the controller before applying

power to the controller on the bus.
To set the device addresses on the controllers:

1.

Set 

all

 of the switches on the address DIP switch

block (128 through 1) to OFF.

2.

Set one or more of the seven address switches (64

through 1) to ON, so that the sum of the switch

numbers set to ON equals the intended device

address. See Table 7.

Set the highest number switch that is less than or equal

to the intended device address to ON. Then continue set-

ting lower-numbered switches until the total equals the

intended address. For example, if the intended device

address is 21, set switch 16 to ON first, then set switch 4

ON, followed by switch 1 (16+4+1= 21).
3.

Set switch 128 to ON 

only

 for controllers on a ZFR/

ZFR Pro Series Wireless Field Bus application. For all

hard-wired SA and FC bus applications, ensure that

switch 128 is set to OFF.

Note: 

Do 

not

 connect a controller with switch 128

set to ON to an active (hard-wired) SA or FC bus.

When a controller with switch 128 set to ON and a

device address from 4 to 127 is connected to a wired

field bus, the entire field bus is rendered inoperable

until the controller is disconnected or switch 128 is

set to OFF.

Note: 

Refer to the 

WNC1800/ZFR182x Pro Series

Wireless Field Bus System Technical Bulletin

(LIT-12012356)

 for more information on device

addresses in wireless applications.

4.

Set a unique and sequential device address for each

of the controllers connected on the SA or FC bus

starting with device address 4.

To ensure the best bus performance, set sequential device

addresses with no gaps in the device address range (4,

5, 6, 7, 8, 9, and so on). The controllers do 

not

 need to be

physically connected on the bus in their numerical device

address order.
5.

Write each field controller's device address on

the white label below the DIP switch block on the

controller's cover.

Table 7 describes the FC bus and SA bus devices

addresses for Johnson Controls MS/TP communications

bus applications.

Table  7: FC bus device address descriptions

Device address

Use on description

0

(Switch 128 Off)

Reserved for FC Bus Supervisory Controller (not for use on field controllers).

1 to 3

(Switch 128 Off)

Reserved for peripheral devices (not for use on field controllers).

4 to 127

(Switch 128 Off)

Used for MS/TP master devices (field) that are hardwired to an SA Bus or FC Bus.

0 to 3

(Switch 128 ON)

Reserved addresses for wired subordinate devices (not for use on field controllers).

Note: 

The controllers ship with switch 128 ON and the remaining address switches off rendering the

controllers wired subordinate devices, which do not operate on MS/TP buses.

4 to 127

(Switch 128 ON)

Valid for MS/TP Master controllers on 

wireless FC Buses only

.

Note: 

Do 

not

 connect a field controller with switch 128 ON to an active (

hard-wired

) SA or FC Bus.

When a controller with switch 128 ON and a device address from 4 to 127 is connected to a wired field

bus, the entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set

to off.

Setting the N2 Controller address to be
greater than 127

N2-configured controllers support the full range of

possible N2deviceaddressesprovidedby the N2 protocol

standard (1-254). However, these controllers require

special configuration for addresses above 127. Use the

following instructions for controllers with addresses

greater than 127.

Note: 

Before you perform this procedure, make

sure that your controller has been converted

from BACnet to N2 protocol first. Refer to the

Modernization Guide for Legacy N2 Controllers

(LIT-12012005)

 for more information.

Note: 

This special configuration is required because

controller addresses above 127 were originally

intended for use with the Wireless Field Bus system.

1.  Disconnect the 24 VAC supply from the

controller.

FEC26 Field Equipment Controllers Installation Guide

17

Summary of Contents for FEC26 Series

Page 1: ...ld Controllers to be either the standard BACnet MS TP or the N2 protocol All new controllers use BACnet MS TP as the default communications protocol Switchable communications protocols in the MS TP models provide a cost effective upgrade and modernization path for customers with existing N2 controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 contr...

Page 2: ...rts included One controller with removable terminal blocks Power SA bus and FC bus are removable One installation instructions sheet Materials and special tools needed Three fasteners appropriate for the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver for securing wires in the ...

Page 3: ... terminal block 11 Sensor Actuator SA Bus Terminal Block See SA bus terminal block 12 Sensor Actuator SA Bus RJ 12 6 pin Modular Jack See SA Bus port 13 Binary Input BI Terminal Block 2 Binary Inputs See Table 3 for more information 14 Universal Input UI Terminal Blocks 6 Universal Inputs See Table 3 for more information 15 LED Status Indicators See Table 9 for more information 16 Field Controller...

Page 4: ...at the top of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bot tom mounting clips out to the extended position and care fully lift the controller off the DIN rail Wall mount applications To mount a cont...

Page 5: ... refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Terminal blocks and bus ports See for terminal block and bus port locations on the controller Observe the following guidelines when wiring a controller Input and Output terminal blocks All of the fixed input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the ...

Page 6: ...rt is connected internally to the SA bus terminal block See Table 5 for more information The Sensor Port pin assignment is shown in Figure 6 Supply power terminal block The 24 VAC supply power terminal block is a gray removable 3 terminal plug that fits into a board mounted jack on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals ...

Page 7: ...t terminals it also references guidelines for determining proper wire sizes and cable lengths In addition to the wiring guidelines observe these guidelines when wiring controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted copper wir...

Page 8: ...4 Analog Input Resistive Mode 0 600k ohms Internal 12 V 15k ohms pull up Qualified Sensors 0 2k ohms potentiometer RTD 1k Nickel Johnson Controls sensor 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 4 INn Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 ...

Page 9: ...ls Note All Analog Output Common terminals OCOMn are isolated from all other commons See Guideline C in Table 4 OUTn Binary Output 24 VAC Triac External Power Source Connects OUTn to OCOMn when activated External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle 40 mA minimum load current BINARY Output Power Selection Jumper positioned to E...

Page 10: ...4 Cable length guidelines for recommended wire sizes for low voltage 30 V Inputs and Outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire A 0 5 mm 24 AWG stranded copper 107 m 350 ft twisted wire 10...

Page 11: ...l blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC Bus Communications COM Signal Reference Common for Bus communications FC BUS SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG stranded 3 wire twisted shielded cable recommended FC BUS Port FC Bus RJ 12 6 Position Modula...

Page 12: ... diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI FEC26 Field Equipment Controllers Installation Guide 12 ...

Page 13: ...ation diagrams Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI or BI 0 10 VDC Output to Actuator External Source CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO FEC26 Field Equipment Controllers Installation Guide 13 ...

Page 14: ...A Output to Actuator CO or AO 4 20 mA Output to Actuator CO or AO Voltage Analog Output AO Analog Output Current AO 24 VAC Triac Output Switch Low External Source CO or AO Incremental Control to Actuator Switch Low Externally Sourced CO or AO FEC26 Field Equipment Controllers Installation Guide 14 ...

Page 15: ...lly Sourced CO or AO Incremental Control to Actuator Switch High Externally Sourced CO or AO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Externally Sourced BO Incremental Control to Actuator Switch High Externally Sourced BO FEC26 Field Equipment Controllers Installation Guide 15 ...

Page 16: ...que device address for each controller on the bus You set a controller s device address by setting the positions of the switches on the DIP switch block at the top of the controller Device addresses 4 through 127 are the valid addresses for these controllers The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address switches Switch 128 is a m...

Page 17: ... to be physically connected on the bus in their numerical device address order 5 Write each field controller s device address on the white label below the DIP switch block on the controller s cover Table 7 describes the FC bus and SA bus devices addresses for Johnson Controls MS TP communications bus applications Table 7 FC bus device address descriptions Device address Use on description 0 Switch...

Page 18: ...ails under the two cover lift tabs on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the cover further to release it from the lower two latches 3 Replace the cover by placing it squarely over the base and then gently and evenly push the cover on to the latches until they snap into the latched ...

Page 19: ...jumpers to the right of the BOs terminal block Figure 12 Example binary outputs and the associated source power jumper positions Universal Input current loop jumpers The Universal Input UI current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and the UI s current loop ...

Page 20: ...er an integral user interface or a remotely connected DIS1710 display refer to the DIS1710 Local Controller Display Technical Bulletin LIT 12011270 Commissioning the Controllers You commission the controllers with CCT software using either a MAP gateway a Bluetooth Wireless Commissioning Converter BCVT a USB dongle with ZigBee Ethernet connection or in BACnet router mode when connected to an NAE o...

Page 21: ... Bus Router Blink 2 Hz Download or Startup in progress not ready for normal operation SA BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Communication lost waiting to join communication ring FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission auto baud ...

Page 22: ... TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 WNC1800 ZFR182x Pro Wireless field Bus System This system is used for installations that support BACnet IP but can also coexist with the ZFR1800 Series when installed under the same supervisor i e network engine Refer to the WNC1800 ZFR182x ProSeries Wireless Field Bus System Product Bulletin LIT 12012320 for a list of ava...

Page 23: ...roller device addresses 1 255 Communications Bus RS 485 field selectable between BACnet MS TP and N2 communications 3 wire FC Bus between supervisory controller and field controllers 4 wire SA Bus between field controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from field controller to bus devices N2 Open Protocol N2 FC Bus 1 0mm 18 AWG stand...

Page 24: ...Emissions Compliant Compliance BACnet International BACnet Testing Laboratories BTL Protocol Revision 9 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable for damages resultin...

Reviews: