Troubleshooting

The following table lists common errors and their solutions.

Error code Description

Solution

ER:01

ERROR_AIR_

SENSOR_OPEN 

•  Check if the built-in temperature sensor is disconnected from the thermostat circuit board or 

damaged. 

•  Contact technical support.

ER:02

ERROR_AIR_

SENSOR_SHORT

•  Check if the built-in temperature sensor is short circuited or damaged. 

•  Contact technical support.

ER:03 

ERROR_AIR_

SENSOR_HI 

Built-in temperature sensor detected a temperature that is too high. 
•  Verify that the thermostat wiring is connected correctly to the FCU or PTAC. 

•  Contact technical support.

ER:04 

ERROR_AIR_

SENSOR_LO

Built-in temperature sensor detected a temperature that is too low. 
•  Verify that the thermostat wiring is connected correctly to the FCU or PTAC. 

•  Contact technical support.

ER:05 

ERROR_REMOTE_

SENSOR_OPEN

•  Check if the remote temperature sensor is disconnected from the thermostat terminals RS 

and SC. If it is, rewire the remote sensor correctly and then power cycle the thermostat. 

•  Check if the remote sensor has malfunctioned or is damaged.

•  Contact technical support.

ER:06  

ERROR_REMOTE_

SENSOR_SHORT

•  Check the remote temperature sensor wiring and check if thermostat terminals RS and 

SC are shorted. If they are, rewire the remote sensor correctly and then power cycle the 

thermostat.

•  Check if the remote sensor is malfunctioned or damaged.

•  Contact technical support.

ER:07 

ERROR_REMOTE_

SENSOR_HI

Remote sensor detected a temperature that is too high. 
•  Verify that the thermostat wiring is connected correctly to the FCU or PTAC. 

•  Verify that the remote sensor is installed correctly in the room or duct. 

•  Contact technical support.

ER:08 

ERROR_REMOTE_

SENSOR_LO

Remote sensor detected a temperature that is too low. 
•  Verify that the thermostat wiring is connected correctly to the FCU or PTAC. 

•  Verify that the remote sensor is installed correctly in the room or duct. 

•  Contact technical support.

ER:09 

ERROR_PIPE_

SENSOR_OPEN

•  Check if the pipe temperature sensor wiring is disconnected from thermostat terminals PS 

and SC. If yes, re-wire the pipe sensor correctly and then power cycle the thermostat.

•  Check if the pipe sensor is malfunctioned or damaged.

•  Contact technical support.

ER:10 

ERROR_PIPE_

SENSOR_SHORT

•  Check the pipe temperature sensor wiring and check if thermostat terminals PS and SC are 

shorted. If it is, rewire the pipe sensor correctly and then power cycle the thermostat.

•  Check if the pipe sensor has malfunctioned or is damaged.

•  Contact technical support.

ER:11 

ERROR_PIPE_

SENSOR_HI

Pipe sensor detected a temperature that is too high. 
•  Verify that the pipe sensor is installed correctly in the pipe. 

•  Contact technical support.

ER:12

ERROR_PIPE_

SENSOR_LO

Pipe sensor detected a temperature that is too low. 
•  Verify that the pipe sensor is installed correctly in the pipe. 

•  Contact technical support.

Table 7: Common errors

Summary of Contents for FCP-PA-701-NF

Page 1: ...in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment...

Page 2: ...t protrude 0 07 in to 0 12 in 2 mm to 3 mm 3 Place the top screw hole of the trim plate over the partly inserted screw in the junction box then pull the wires through the trim plate opening 4 Slide th...

Page 3: ...iring Figure 5 Attaching the back housing to the trim plate Figure 4 Attaching the trim plate to the junction box Figure 7 2 pipe fan coil unit Figure 8 4 Pipe fan coil unit Figure 6 Attaching the fro...

Page 4: ...Conventional PTAC Profile Remote sensor Pipe sensor System type 2 pipe FCU with aux heat Available modes 1 Heat only 2 Cool only 3 Heat and cool with auto 4 Heat and cool without auto Pipe state cale...

Page 5: ...ed mode manually HEAT and COOL mode Mode for 5 seconds Table 3 Button combinations Table 2 Preset configuration profiles part 2 of 2 Control mode FCP has four control modes OFF HEAT COOL AUTO The avai...

Page 6: ...configuration settings Press Mode to scroll through the menu and press Up or Down to change options Press Mode to confirm a change Press Back to move backward in the menu or press Mode at the end of...

Page 7: ...location 0 in room 1 in duct 0 26 Remote sensor type 0 type II 1 type III 0 27 Pipe sensor type 0 type II 1 type III 0 28 Pipe state calendar ON OFF OFF 29 Heat to cool day unavailable if pipe state c...

Page 8: ...or Down to set the required period and temperature Repeat this step until you set all the schedule settings 4 Press Mode to save the settings and return to Set Sche menu 5 Press Up or Down to navigate...

Page 9: ...ck if the remote sensor is malfunctioned or damaged Contact technical support ER 07 ERROR_REMOTE_ SENSOR_HI Remote sensor detected a temperature that is too high Verify that the thermostat wiring is c...

Page 10: ...put Set back NC NO dry contact switch Local temperature sensor type NTC temperature sensor accurate to 1 F 0 6 C at 77 F 25 C Remote temperature sensor type NTC temperature sensor accurate to 2 F 1 2...

Reviews: