Environmental Guidelines
DVN 5000
24-10520-22 Rev. –
39
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2009 Johnson Controls, Inc.
Thermal Solutions
Figure 26: Vent Blockers
Careful placement of vent blockers, as part of your proper thermal management
planning, helps prevent the short-circuiting of airflow in rack enclosures. Vent
blockers magnetized on one side help force the heated enclosure air out through
top-mounted exhaust fans.
Upper Inside Side Panel
Upper Inside Rear Door
Enclosure Upper Faces
Vibration
Hard drives are very sensitive to vibration from other drives and nearby fans. This
causes the read/write head to stop momentarily, which slows the system, or can even
cause a head crash. Mounting DVNs near the top of the rack causes more vibration
and early disk drive failures. The three year life is reduced to two years in actual
cases observed.