Appendix B: SEC parameters for DSH024C–
DSH120C units
Table 32: SEC parameters for DSH024C-060C units with single speed evaporator fan
Menu/sub-menu
Parameter
Factory value
Standard
T-Stat Only
Yes
# Refrig Sys
1
Commission
Options
# Ht Pump Stgs
0
Occ Mode
1
External
OCC
Off Dur Unocc
No
Clg-En
Yes
# Clg Stgs
1
C1-En
Yes
Low Amb-En
2
No
Lead Lag-En
3
No
Clg OAT Cutout-En
Yes
Clg OAT Cutout
45
Clg Adap Tune-En
No
SAT Cool Limit-En
Yes
Sat Cool Limit-SP
45
Cooling
Freeze-SP
26
Htg-En
4
No
Heating
# Htg Stgs
0
Fan Ctl-Type
Single Speed
Fan On Dly Cool
0
Details
Fan
Setup
Fan Off Dly Cool
45
Note:
1. Factory shipped units equipped with Occ jumper on UCB
2. Do not enable low ambient
3. Do not enable LeadLag
4. Field supplied option
Model DSH024C–120C Horizontal R-410A Air Conditioning Units C-Generation Smart Equipment Controller