Table 12: DSH036C – Condenser fan performance
Available external static pressure – iwg
0.0
0.2
0.4
0.6
0.8
Outdoor CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive
Hi-static drive
2100
542
0.31
631
0.40
717
0.49
799
0.58
875
0.68
Table 13: DSH048C – Supply air blower performance
Available external static pressure – iwg
1
0.0
0.1
0.2
0.3
0.4
0.6
0.8
1.0
1.2
1.4
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Low static drive
3
Factory drive + 0.75 HP
Hi-static drive + 0.75 HP
1200
381 0.11 451 0.14 511 0.16 569 0.20 620 0.24 717 0.30 803 0.36 882 0.44 954 0.51 1023 0.60
1400
447 0.18 506 0.21 561 0.24 612 0.28 660 0.31 750 0.39 831 0.46 906 0.55 977 0.64
-
-
1600
511 0.25 562 0.30 612 0.34 658 0.38 703 0.43 786 0.50 863 0.59 935 0.68 1002 0.78
-
-
1800
575 0.36 621 0.41 666 0.45 708 0.50 749 0.55 826 0.64 898 0.74 967 0.84
-
-
-
-
2000
637 0.50 680 0.55 720 0.60 760 0.65 797 0.70 869 0.80 937 0.91 1001 1.00
-
-
-
-
Note:
1. Blower performance includes evaporator coil and 2-inch filters.
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may
occur. Decrease airflow downward as necessary.
3. Field supplied low static drive.
Table 14: DSH048C – Condenser fan performance
Available external static pressure – iwg
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP RPM
BHP
RPM
BHP
Standard factory drive
Hi-static drive
2400
503
0.40
577
0.50
645
0.60
708
0.71
767
0.82
822
0.93
875
1.05
Table 15: DSH060C – Supply air blower performance
Available external static pressure – iwg
1
0.0
0.1
0.2
0.3
0.4
0.6
0.8
1.0
1.2
1.4
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Low static
drive
3
Factory drive + 1.5 HP
Hi-static drive + 2.0 HP
1600
511 0.25 562 0.30 612 0.34 658 0.38 703 0.43 786 0.50 863 0.59 935 0.68 1002 0.78 1066 0.86
1800
575 0.36 620 0.41 666 0.45 708 0.50 749 0.55 826 0.64 898 0.74 967 0.84 1031 0.94 1092 1.04
2000
637 0.50 680 0.55 720 0.60 760 0.65 797 0.70 869 0.80 937 0.91 1001 1.01 1063 1.13 1121 1.24
2200
699 0.66 739 0.71 776 0.78 813 0.83 847 0.89 914 1.00 978 1.11 1039 1.23 1098 1.34
-
-
2400
765 0.86 800 0.93 835 0.99 868 1.04 901 1.10 964 1.23 1024 1.35 1082 1.48
-
-
-
-
Note:
1. Blower performance includes evaporator coil and 2-inch filters.
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may
occur. Decrease airflow downward as necessary.
3. Field supplied low static drive.