background image

J500-41-00 

I56-2199-003R

[

4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

  To install sampling tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 

8 feet is accomplished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the 
sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.

Install the sampling tube as follows:

1.  Drill a 

3

4

-inch hole in the duct directly opposite the hole already drilled for the sampling tube. Make sure the hole is 1

 to 2

″ 

below the inlet hole on 

the opposite side of the duct to allow for moisture drainage.

2.  Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air 

flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.

3.  From inside the duct, couple the other sections of the sampling tube to the section already installed using the 

1

2

-inch conduit fittings supplied. Make 

sure that the holes on both of the sampling tubes are lined up and facing into the air flow.

4.  Trim the end of the tube protruding through the duct so that 1

 to 2

 of the tube extend outside the duct. Plug this end with the end cap and tape 

closed any holes in the protruding section of the tube. Be sure to seal the duct where the tube protrudes.

NOTE:

  An alternate method to using the ST-10 is to use two ST-5 sampling tubes. Remove the flange from one of the tubes and install as described 

above. After the installation, use electrical tape to close off some of the sampling holes so that there are a total of 10 to 12 holes spaced as 
evenly as possible across the width of the duct.

NOTE:

  Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch 

floor flange (available at most plumbing supply stores) may be used to fasten the sampling tube to the other side of the duct. When using 
the flange/connector mounting technique, drill a 1-inch to 1

1

4

-inch hole where the flange will be used. 

[5] Install The Filters 

To install the sampling tube filters, simply push the filters into the sampling and exhaust tube holes, as shown in Figure 6. If a metal sampling tube is 
used, install the filters over the tube end.

Figure 6. Sampling tube filter installation:

[6] Field Wiring Installation Guidelines

All  wiring  must  be  installed  in  compliance  with  the  National  Electrical 
Code and the local codes having jurisdiction. Proper wire gauges should 
be  used.  The  conductors  used  to  connect  smoke  detectors  to  control 
panels  and  accessory  devices  should  be  color-coded  to  prevent  wiring 
mistakes. Improper connections can prevent a system from responding 
properly in the event of a fire.

CAUTION

Filters  require  periodic  cleaning  or  replacement,  depending  on  the 
amount of dust and dirt accumulated. Visually inspect the filters at least 
quarterly; inspect them more often if the dust accumulation warrants it. 
See  Section  [9.1.2]  for  more  information.  Replacement  filters  can  be 
ordered (filter P/N F36-09-11).

For signal wiring, (the wiring between detectors or from detectors to auxiliary devices), it is usually recommended that single conductor wire be no 
smaller than 18 gauge. The duct smoke detector terminals accommodate wire sizes up to 12 gauge. The last foot of conduit should be flexible conduit 
(available in electrical supply houses), which facilitates easier installation and puts less strain on the conduit holes in the housing. Solid conduit con-
nections may be used if desired.

Smoke detectors and alarm system control panels have specifications for Signaling-Line Circuit (SLC) wiring. Consult the control panel manufacturer’s 
specifications for wiring requirements for the particular model control panel being used before wiring the detector loop.

The DH300RPL detector is designed for ease of wiring. The housing provides a terminal strip with clamping plates.

Wiring connections are made by stripping about 

3

8

-inch of insulation from the end of the wire, sliding the bare end under the plate, and tightening the 

clamping plate screw. 

Two LEDs on each duct smoke detector may light, if programmed by the system control panel, to provide a local, visible indication.  Remote LED 
annunciator capability is available as an option. Each duct smoke detector can only be wired to one remote accessory.

H0131-00

Summary of Contents for DH300RPL

Page 1: ... it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The DH300RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The DH300RPL incorporates a cover tamp...

Page 2: ...Installation for ducts more than 8 feet wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The DH300RPL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute Be sure to che...

Page 3: ...opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2...

Page 4: ... where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical...

Page 5: ...in duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or system under test to prevent unwanted alarms 9 1 Smoke Entry Tests 9 1 1 Air...

Page 6: ...ces to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differ ential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests...

Page 7: ...and that the system will temporarily be out of ser vice Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If...

Page 8: ...different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To keep your equipment in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of Chapter 7 of NFPA 72 the National Fire Alarm Code shall be followed A preventative maintenance agre...

Reviews: