background image

CAUTION: Do not overtighten the screws.

[4] Sampling Tube Installation for Ducts Greater Than 1

1

2

 Feet 

Wide

The sampling tube is identified by a series of air inlet holes on the tube. 
A plastic tube is included for ducts up to 1

1

2

 

 feet wide. All other lengths 

must be purchased separately. Order the correct length, as specified in 
Table 1, for width of the duct where it will be installed. It is recommended 
that the sampling tube length extend at least 

2

3

 across the duct width for 

optimal performance. The exhaust tube is molded onto the base of the 
duct housing, and the A2440-00 Exhaust Tube Extension is available as 
an  accessory  in  those  cases  where  the  molded  exhaust  port  does  not 
extend at least 2 inches into the duct. 

The sampling tube is always installed with the air inlet holes facing into 
the  air  flow.  To  assist  proper  installation,  the  tube’s  mounting  flange  is 
marked with an arrow. Make sure the sampling tube is mounted so that 
the  arrow  points  into  the  air  flow  (see  Figure  4).  Figure  5  shows  the 
various combinations of tube mounting configurations with respect to air 
flow. Mounting the detector housing in a vertical orientation is acceptable, 
provided that a metal sampling tube is used and the air flows directly into 
the sampling tube holes as indicated in Figure 4.

[4.1] Installation For Ducts Greater Than 1

1

2

 Feet But Less Than 8 

Feet Wide

1. 

If the tube is longer than the width of the air duct,

 drill a 

3

4

 hole in the 

duct opposite the hole already cut for the sampling tube. Make sure the 
hole is 1

 to 2

 below the inlet hole on the opposite side of the duct to 

allow moisture drainage away from the detector. 

If the tube is shorter 

than  the  width  of  the  air  duct,

  install  the  end  cap    into  the  sampling 

tube  as  shown  in  Figure  4.  Sampling  tubes  over  3  ft.  long  must  be 
supported at the end opposite the duct smoke detector.

2.  Slide the tube into the housing bushing that meets the air flow first. 

Position the tube so that the arrow points into the air flow, as shown 
in Figure 4. 

3.  Secure the tube flange to the housing bushing with two #6 self-tapping 

screws.

4.  For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct. If there are more than 2 holes in 
the  section  of  the  tube  extending  out  of  the  duct,  select  a  different 
length using Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1

 to 2

 of the tube extend outside the duct. 

Plug this end with the end cap and tape closed any holes in the pro-
truding section of the tube. Be sure to seal the duct where the tube 
protrudes.

NOTE:

 The sampling tube end cap is critical to the proper operation of 

the duct smoke detectors. The end cap is needed to create the 
proper air flow to the sensor of the duct smoke detector

.

J500-41-00 

I56-2199-003R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over sampling 
tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

Table 1. Sampling tubes recommended for different 
duct widths:

 

Outside Duct Width 

Sampling Tube Recommended*

 

1 to 2 ft. (0.3 to 0.6 m) 

ST-1.5

 

2 to 4 ft. (0.6 to 1.2 m) 

ST-3

 

4 to 8 ft. (1.2 to 2.4 m) 

ST-5

 

8 to 12 ft. (2.4 to 3.7 m) 

ST-10

*Must extend a minimum of 

2

3

 the duct width

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes can be installed in 
orientations C and D.

H0107-00

H0108-02

H0109-00

H0109-01

Summary of Contents for DH300RPL

Page 1: ... it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The DH300RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The DH300RPL incorporates a cover tamp...

Page 2: ...Installation for ducts more than 8 feet wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The DH300RPL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute Be sure to che...

Page 3: ...opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2...

Page 4: ... where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical...

Page 5: ...in duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or system under test to prevent unwanted alarms 9 1 Smoke Entry Tests 9 1 1 Air...

Page 6: ...ces to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differ ential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests...

Page 7: ...and that the system will temporarily be out of ser vice Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If...

Page 8: ...different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To keep your equipment in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of Chapter 7 of NFPA 72 the National Fire Alarm Code shall be followed A preventative maintenance agre...

Reviews: