Checking the Motion Sensor
1. Perform a motion detection action (such as waving a hand) under the motion sensor of the
selected indoor unit for approximately 10 to 15 seconds.
2. Check the value of “q3” to "q6" after 30 seconds* from starting the motion detection at Step 1.
The detection information from the motion sensor against the motion detection is displayed at a
range of 0% to 100%.
* The communication cable between the indoor unit and the wired controller is on a 30-second cycle.
Timing for motion detection and the detected information display is shown below.
3. Check that the value of “q3” to "q6" is neither 0% nor 100%.
If the value displayed is 0% or 100%, repeat the procedures from Step 1. If the same value
reappears, it may be a malfunction of the motion sensor.
NOTE:
Refer to the operation manual for indoor
unit settings, setup of the motion sensor.
(“Motion Sensor Setting”, “If Absent” and
“Check Interval” can be set.)
30 sec.
Motion Detection
Detected Information
Display
(for 30 seconds)
: Communication Data
Cycle 30 seconds.
30 sec.
e. Though temperature recordings by the thermistors are invalid during the test run phase, the
protection devices are valid.
f. For VRF System
According to the label; “Checking Method by 7-Segment Display” affixed to the inside of the front
cover of the outdoor unit, check temperature, pressure, and operation frequency, and interconnected
indoor unit numbers by 7-Segment displays.
g. To complete Test Run, press “ On/Off” again or wait for the
set Test Run time to pass.
When changing the Test Run time, press “ ” or “ ” to select
“Test Time”. Then, set the test run time (30 to 600 minutes) by
pressing “ ” or “ ”.
Adj.
Sel.
OFF
Test Run: 2 units
MODE
SPEED
AUTO
COOL
LOUV.
Test Time
120min
Inverter
60Hz