background image

5. Secure the mounting base to the wall, using at least

two field-supplied screws. See Figure 3.

Figure 3: Route the cable from behind and mount the wall

plate

Note: 

When you bring the cable through the

wall, seal the cable opening. If left unsealed,

the hole allows air from outside the room into

the transmitter and affects the measurement

readings. For example, fresh concrete binds CO

2

and can cause low readings, especially in new

buildings.

Connecting the cable to the mounting
base

About this task:

Connect the wires from the cable to the screw terminals

on the mounting base. The terminal assignments are

marked next to the screw terminals. Maximum wire size is

2 mm

2

, AWG 14.

1. Strip 1/4 in. (6.35 mm) of insulation from the ends

of the power and output signal wires.

Note: 

To prevent a short circuit, make sure that

the wires are stripped to the correct length

and fully inserted into the terminal blocks. If

using shielded cable, ensure that the shield is

protected from contact with components on the

top or bottom side of the printed circuit board.

Failure to follow proper wiring procedures may

cause the transmitter to fail.

2. Connect the wires to the mounting base screw

terminals as shown in Figure 4.

Figure 4: Screw terminals

Note: 

The transmitter generates both voltage

and current output. Each output has its own

individual positive screw terminal.

Power supply requirements

The transmitter requires a 24 VAC/VDC, Class 2 power

supply. Although the power input includes a halfwave

rectifier, use a DC supply to avoid excessive current peaks.

Connections to a 24 VAC power supply

Connecting more than one transmitter to a single 24 VAC

transformer forms a common loop and increases the risk

of a short circuit. To prevent this, use a separate floating

supply for each transmitter. See Figure 5.

Figure 5: Connecting separate AC supplies

If several transmitters share a common transformer,

always connect the transmitter common to the same

side of the transformer to maintain the polarity. A shared

common line at the controller can cause a short circuit if

the phase is not the same. See Figure 6.

CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature Transmitters Installation Guide

3

Summary of Contents for CD-W00-0-2 Series

Page 1: ...uire de brouillage et 2 L utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Installation Important The CD W00 x0 2 Series Wall Mount CO2 and Temperature Transmitters are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could...

Page 2: ... a cable ferrule to the cable end If the distance between the sensor and the controller is over 3 meters 9 8 feet use shielded cable Connect the shield at the controller end of the cable Location selection When mounting wall model transmitters Select a location that represents the area of interest Do not install the transmitter on the ceiling Avoid placing the transmitter near heat and moisture so...

Page 3: ...ts on the top or bottom side of the printed circuit board Failure to follow proper wiring procedures may cause the transmitter to fail 2 Connect the wires to the mounting base screw terminals as shown in Figure 4 Figure 4 Screw terminals Note The transmitter generates both voltage and current output Each output has its own individual positive screw terminal Power supply requirements The transmitte...

Page 4: ...eset the 2 000 ppm value using the controller s compensation factor CF shown in Figure 7 or Figure 8 Calculate the corrected value Corrected Value CF x 2 000 For example if the sensor is situated at an altitude of 3 000 ft 914 4 m above sea level the CF is 1 10 See Figure 7 or Figure 8 The corrected value is Corrected Value 1 10 x 2 000 ppm 2 200 ppm Note For altitude compensation only adjust the ...

Page 5: ... mA and 0 to 10 VDC Maximum output current 21 mA maximum output voltage 11 V Resolution of analog outputs 0 3 ppm CO2 External load Minimum 1 000 ohms load resistance for 0 to 10 V Maximum 600 ohm load resistance for 4 to 20 mA Power supply range 24 VAC 20 50 60 Hz 18 to 30 VDC Class 2 Power consumption 1 0W Average excluding current output consumption Current consumption 100 mA peak on AC power 4...

Page 6: ...ht Dieser Sensor Transmitter kann nur wandmontiert eingesetzt werden Der elektrische Anschluß ist nach den örtlichen Vorschriften durch autorisiertes Personal durchzuführen Versorgungsspannung und Niederspannung sind getrennt zuzuführen Bei Verwendung von flexiblen Leitungen sind Kabelschuhe zu verwenden Überprüfen Sie alle Kabelverbindungen bevor Sie den Antrieb einschalten Der Kontakt mit Kompon...

Page 7: ...nslutningen ska utföras av behörig personal i enlighet med de lokala föreskrifterna Försörjningsspänning och lågspänning ska tillföras åtskilt Vid användning av flexibla ledningar ska kabelskor användas Kontrollera alla kabelförbindelser innan du tillkopplar ställdonet Kontakt med komponenter med farlig spänning kan ge elektriska stötar som kan orsaka allvarliga eller livshotande personskador Kort...

Page 8: ...ь причиной несчастного случая или повреждения оборудования если кабель между Датчик и контроллером составляет более 3 метров то должен быть экранирован Экран следует заземлять в одной точке на стороне контроллера Сохраните этот документ Portuguese Certifique se que a fonte de alimentação é compatível com a fonte de alimentação especificada na secção de Especificação Técnica Este sensor transmissor...

Page 9: ...s com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnsoncontrols com contact us Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PR...

Page 10: ... 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice ...

Reviews: