AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
35
BACnet Temperature Alarm Configuration
The BACnet Temperature Alarm Configuration submenu is only available when BACnet is on (see
). In this submenu, you can configure temperature parameters including high and low alarms,
setpoints, and alarm delay.
Table 16: BACnet Temperature Alarm Configuration Submenu Selections and Configurable Options (Part 1
of 2)
BACnet Temperature
Alarm Configuration
Submenu Selections
Configurable Options
Alarm Low On/Off
Select On or Off.
Alarm High On/Off
Select On or Off.
Alarm Low Setpoint
Choose a value the temperature must go below for an alarm condition to exist.
Alarm High Setpoint
Choose a value the temperature must surpass for an alarm condition to exist.