Technical Specifications
AD-1252 Thermal Dispersion Probe Airflow Measuring System
Probe
Airfoil shaped 2 x 3/4 in. 6063T5 aluminum
Thermistor
Bead-in-glass type
Size Range
8 x 8 to 120 x 120 in.
Brackets
0.080 Aluminum
Installed Airflow Accuracy
2% of reading
Repeatability
0.25%
Measurement Units
Inch-Pound (I.P.) or International System (S.I.)
Sensor Distribution
Equal Area
Calibrated Range
40 to 4,000 FPM (12 to 1,219 MPM)
Temperature Sensor Accuracy
0.10º F
Sensor Temperature Range
-25 to 140
F (-32 to 60
C)
Humidity Range
0 to 99% RH, noncondensing
Maximum Number Sensors
16
Power Requirement
Dedicated 24 VAC transformer of appropriate VA rating is required.
Power Consumption
4 probes with 4 sensors: 65 VA; 3 probes with 4 sensors: 48 VA;
2 probes with 4 sensors: 35 VA; 1 probe with 4 sensors: 17 VA
Transmitter Chassis
0.080 Aluminum
Output Signals
4 to 20 mA standard, 2 to 10 VDC requires 499 ohm resistor across output terminals.
Output Signal Adjustments
Field adjustable offset/gain
Display
16x2 character LCD (airflow, temperature and diagnostics)
Velocity Requirements
Minimum 40 FPM (12 MPM)
Maximum 4,000 FPM (1,219 MPM)
Pressure Drop
Four 48 in. (122 cm) long probes in 48 x 48 in. (122 x 122 cm) duct: 0.1 in. w.g.
Approximate Weight
Controller: 2.9 lb (1.32 kg)
Sensor: 1 lb (0.45 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA