AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions
18
Adjust mA Output Filter Value
This option submenu allows the user to adjust the mA
filter value used to speed up or slow down the mA
output rate. Use the default value of 0.35 for the
majority of applications. Use an mA filter value of 0.5
when an instantaneous output signal is required for
applications such as fan tracking. Decrease the value if
the data is erratic.
The mA output filter responds to the air flow calculation
and is applied to the 4 to 20 mA output signal only. As
the value decreases, filtering increases. See Figure 28.
Auto Reset
This option submenu allows the user to enable or
disable the automatic reset function. See Figure 29.
Auto Reset is a software timer that triggers a system
reset only if the main program encounters a fault
condition or the software code execution encounters an
endless loop. Auto Reset brings the system back from
an unresponsive state into normal operation and
eliminates the need for constant user monitoring of the
software.
The default setting is ON. Set Auto Reset to OFF for
troubleshooting. If normal operation is interrupted when
Auto Reset is OFF, manually cycle power to the control
to restore normal operation.
Temp Display
This option submenu allows the user to disable the
temperature display. The default setting is ON. When
the temperature display is OFF, the display only shows
the air movement measurement. See Figure 30.
Troubleshooting
During normal operation, two LEDs illuminate at the
RJ45 connector on the DMPR-RA002 Electronic
Controller. The left (green) LED indicates that the
electronic controller has properly identified the probe.
The right (amber) LED illuminates each time the
electronic controller communicates with the connected
thermal dispersion probe. See Figure 12.
If the right (amber) LED does not blink, reset the
electronic controller by cycling the power switch OFF
and then ON. See Figure 12.
Figure 28: Adjust mA Output Filter Value
Submenu
UP
SW3
DOWN
SW4
UP
SW3
ENTER
SW5
ADJUST mA OUTPUT
FILTER VALUE
FILTER VALUE
:0.35
AUTO RESET
F
IG
:s
b
m
n
_mA
_ou
pt_fl
tr
_
v
a
l
Figure 29: Auto Reset Submenu
UP
SW3
DOWN
SW4
ENTER
SW5
ENTER
SW5
ENTER
SW5
AUTO RESET
AUTO RESET
:ON
AUTO RESET
:OFF
TEMP DISPLAY
TEMP DISPLAY
F
IG
:s
b
m
n_auto_r
s
t
Figure 30: Temp Display Submenu
UP
SW3
DOWN
SW4
ENTER
SW5
ENTER
SW5
ENTER
SW5
TEMP DISPLAY
TEMP DISPLAY
:ON
TEMP DISPLAY
:OFF
RESET SETTINGS
RESET SETTINGS
F
IG
:s
b
mn
_temp_
ds
p
ly